Page 1
ER3000 Electronic Pressure Controller User Manual...
Page 2
During the Warranty Period, Tescom will, in its sole discretion, repair or replace, free of charge at its factory in Minnesota, any product or part thereof that is found by Tescom, after reasonable notification by the Initial Purchaser, to have been defective in materials or workmanship.
Page 3
COMPATIBILITY Tescom may suggest material for use with specific media upon request. Suggestions are based on technical compatibility resources through associations and manufacturers. Tescom does NOT guarantee materials to be compatible with specific media - THIS IS THE RESPONSIBILITY OF THE USER! Users must test under operating conditions to determine suitability of materials in an application.
4.4.4 Connect RS485 Interface Connections -------------------------------- 15 4.4.5 Install the “ER3000 (CVI)” Windows Program---------------------- 15 4.4.6 Communicate to the ER3000, using the ER3000 (CVI) Windows Program 15 4.4.7 Connect Transducer Wiring--------------------------------------------- 16 4.4.8 Connect Pressure to the System ---------------------------------------- 16 4.4.9...
Manual mode allows for direct control of the solenoid valves (useful for troubleshooting the system). In summary, the ER3000 electronic pressure regulator is easy to get up and running, yet offers the flexibility required by the most demanding user.
NEMA 4X. To prevent any interference from electromagnetic radiation, use rigid metal conduit to enclose the wiring entering the ER3000. Two 1/2NPT wire ports have been provided for this purpose. If unused, properly seal with a metal plug. 2.2 Media The preferred media is clean, dry instrument grade air or nitrogen.
2.8 Accuracy Room temp.: 0.1% of span max Temp. effects: 0.002%/°F of span max. 2.9 Response Time Rise Time: 257ms. - 10 psi to 90 psi Fall Time: 552ms. - 90 psi to 10 psi Note: Step response into dead-end system (1 cubic inch volume). 2.10 Ports Conduit: 1/2”...
3. ER3000 PART NUMBERING SYSTEM Standard features: RS485 communications included. 1/8” inlet and exhaust ports, 1/4” controlled output port. Maximum inlet pressure = 120 psig. 0 to 100 psig internal sensor. Windows/DOS software package included. 24 VDC power required. As the table below indicates, other sensor ranges are available. Please consult the factory for special modifications or requirements.
4. INSTALLATION The ER3000 has a number of variations and wiring options. The following pages of the installation section detail a typical installation and many of those options. Note: Installation of explosion proof models shall be in accordance with the specifications of the standards shown on the metal tag.
4.2 Voltage/Current Select Jumpers Figure 1 shows the J5 voltage/current select jumpers location on the ER3000. Use them to select between 4-20mA and 1-5V. The 0-10V models of the ER3000 do not have the jumpers. The jumper on the bottom board is for factory installation of the embedded software only and the jumper should not be installed for normal operation.
4.3 Basic ER3000 to PC Wiring The necessary wiring for the ER3000 communicating to a PC is shown in Figure 2. A PC is typically used to communicate to the ER3000 digitally, but any device capable of the interface protocol could be used, such as a PLC.
4.4 Setting up a Typical ER3000 Pressure Control System One of the most commonly used modes of operation is shown in Figure 3. The configuration shows the ER3000 with a 24 Volt power supply, pressure regulator, 4-20mA transducer, RS232/RS485 converter, and an optional 25-9 pin adapter cable.
ER3000. For details, reference mechanical drawings at the back of the manual. 4.4.3 Connect the Power Supply Connect a 24 Volt power supply to the ER3000, as shown in Figure 2. Power up the ER3000. Visually check the LED indicators to ensure that power is supplied to the ER3000.
4.4.8 Connect Pressure to the System Figure 3 illustrates the typical pressure connections for the ER3000. ER3000 inlet pressure is the supply pressure (max 120 psi). The exhaust port on the ER3000 is used for venting when a pressure reduction is required. The inlet pressure to the regulator depends on the capability of the regulator and the system requirements.
The wiring for the two-wire transducer is shown in Figure 3. The wiring for the three wire and four wire transducers are shown in Figure 4 and Figure 5 respectively. Connect the ER3000 to the transducer, or other feedback source, as shown in the respective diagrams.
4.5.2 Analog Setpoint Source Check to ensure that the analog setpoint voltage/current select jumper, J5:1, is installed for 4-20mA or removed for 1-5V operation. There is no jumper on the 0-10V external feedback models. Figure 6 and Figure 7 show how to provide a 4-20mA analog setpoint from a PC D/A card or a PLC D/A module.
The 0-1V range can be programmed to be a failsafe condition for 1-5V ER3000’s. Refer to section 5.4, Failsafe Limits, for more information on failsafe. Note: The ER3000 cannot directly provide a 0-10 volt signal. An external 10- volt supply must be used for power. Figure 8: Potentiometer Analog Setpoint NOTE: Wire power as shown in figures 2 &...
4.5.3 Monitor the Feedback Signal The feedback signal can be monitored using an A/D card in the PC, or a PLC. Although, currently available through the RS485 interface, the user may find it more convenient to directly read the transducer analog output. This would be beneficial when adding to existing system software which performs system control, data acquisition, etc.
In order to avoid producing ground loops, it may be necessary in some systems to monitor the voltage produced across the ER3000’s internal 250 Ω resistor rather than breaking into the 4-20 mAmp loop. Figure 12: Monitor voltage produced by 4-20 mAmp External Feedback NOTE: Wire power as shown in figures 2 &...
Figure shows a simple wiring method of controlling a profile, without the need for a computer. Once the profile is downloaded into the ER3000, it can be started or stopped with a toggle switch. The Digital Input pushbutton may be used if the “Digital Input”...
NOTE: Wire power as shown in figures 2 & 3 4.5.6 Monitor Analog Signals The ER3000 can monitor a number of analog signals. This is quite useful in data acquisition systems to perform trend analysis on the system. Figure 15 shows two transducers (e.g.
4.5.8 Digital Outputs The ER3000’s can provide digital outputs to the rest of the system. The outputs can be toggled using a PC computer program or as part of a pressure profile. This can be used to trigger a process in another part of the system or simply turn on a light bulb or sound an alarm.
4.5.9 Monitor Internal Sensor using the Analog Output The ER3000 provides the capability of monitoring the internal sensor. Figure 18 shows the 4-20 mA wiring option. This feature is only available on models that supply the analog output of the internal sensor, as referenced in Section 3 (ER3000 Model Description).
(normally the exhaust vents to ambient). In a typical application, the ER3000 loads the dome of a dome loaded regulator (air to open and a venting type regulator for the purpose of this example) and senses pressure from a transducer mounted downstream in the process, as shown in Figure 3.
5.2.2 External Feedback Mode The external feedback mode uses a user supplied external transducer to control the process pressure. This mode is typically used when using the ER3000 to load the dome of a mechanical air actuated regulator or control valve. Control of...
5.4 Failsafe Limits Another function of the ER3000 is to detect when programmable limits are exceeded. Limits can be set on the following variables: • Analog setpoint. • Internal feedback. • External feedback. • Inner loop error signal. • Outer loop error signal.
Tune the Typical Application This tuning procedure utilizes the Windows Tuning program ER3000 (CVI) and is taken from the ER3000 (CVI) On Line Help. It applies to the above typical application using external feedback. To begin, it should be realized that the tuning of PID controllers is learned with experience.
Page 36
10, 20, 50, 100, 200, 500, 1000 ... can be tried until an optimal value is obtained. At this point it should be noted that the ER3000 provides a unique integral limiting feature ('Minimum Outer Integral' and 'Maximum Outer Integral'). This allows for using large integral terms without creating excessive overshoot.
Page 37
The following is an example sequence of tuning steps. First a very undertuned response is shown (note size of proportional term). Next the proportional term is increased, however, overshoot and ringing results: 36 ER3000 User Manual...
Page 38
Now, some Derivative is introduced. Note the decrease in overshoot. However, if we zoom in on the horizontal axis between 1750 and 2000 psi, we notice that a small offset remains. 6. Tuning Procedure 37...
Page 39
The system can be further tuned by selecting different pressure settings and testing the response. The final tuning should be done at pressures that are representative of how the system will be operated. 38 ER3000 User Manual...
7.1 Zero/span The calibration of the unit may be changed by adjusting the zero and span settings of the ER3000. The Zero and Span settings are found on the Miscellaneous Screen of the Windows ER3000 program. Normally, the zero and span do not need adjustment since the unit has been factory calibrated.
There are also two subdirectories, DLL and DLL32. The files in these directories are used to create the 16 and 32 bit versions of the Tescom DLL. 8.3 Tescom Protocol (Provides Custom Software Support) The Tescom Protocol used to interface to the ER3000 is non-proprietary. A description of the protocol is given in PROTOCOL.DOC in the subdirectory...
WriteNetVar - This function is used to write any of the ER3000 internal variables. ReadNetVar - This function is used to read any of the ER3000 internal variables. WriteProfileSegment - This function is used to write any of the ER3000 profile segments, 1-32.
Excel to plot the profile. The programs and their descriptions are documented in README.DOC residing in TESCOM2\PROFILE directory. It should be noted that this method of profiling writes to the ER3000 setpoint variable, which is different then the embedded profiling capability of the ER3000.
Test_pr.exe resides in the Debug directory. This program can be used as a simple test for the user to check for node and serial numbers, version of software, and communication port. This program should be used as part of the troubleshooting steps described in Section 10, Troubleshooting. 9. ER3000 Internal Variables 43...
9. ER3000 INTERNAL VARIABLES The ER3000 has a number of internal variables which can be accessed via the RS485 interface. The most commonly used variables are listed below. The variable index number, name, and description are shown. The index number is...
16 ID_OUTER_D_COEF1 - This is the D-term, derivative constant, for the outer loop. 49 ID_OUTER_INTEGRAL_MINIMUM - This is the minimum value allowed for the integral sum on the outer loop. 9. ER3000 Internal Variables 45...
- after linearization has been applied to the raw signal. 85 ID_AD_EXTRA1_TOGGLE - This variable is used to adjust the level that the ER3000 interprets the ID_COMPENSATED_EXTRA_AD1 variable as a logical 0 or a logical 1. 86 ID_AD_EXTRA2_TOGGLE - This variable is used to adjust the level that the ER3000 interprets the ID_COMPENSATED_EXTRA_AD2 variable as a logical 0 or a logical 1.
111 ID_UI_UNITS_CHAR4 range units (i.e. psi.). 114 ID_UI_SCALE_MIN_LO The scale minimum and scale maximum 115 ID_UI_SCALE_MIN_HI variables are used by supplied software to 116 ID_UI_SCALE_MAX_LO show minimum and maximum ranges. 117 ID_UI_SCALE_MAX_HI 9. ER3000 Internal Variables 47...
12 ID_PWM_SHUTOFF_FLAG – This flag is only active if ID_RTTASK_DELAY (variable #13) is not a 0 or 1 and designates what the ER3000 will send to the PWM every 25ms while it is delaying. 0 => Write the previously computed value to the PWM 1 =>...
34 ID_OUTPUT - This is the value of the output from the controller. It is this value which controls the ER3000’s valves. A positive number will open the inlet valve and a negative number will open the outlet valve.
Page 54
The exceptions are the sensor range variables, 108-111 and 114-117, and the profile restart, variable 119. The profile restart variable is the only one that is used by the embedded software. Table 3 (continued): ER3000 Internal Variables Variable Name and Number Type...
Table 4: LED Indicators Terminal (Top) Board LED1, red = On continuously, if power is supplied to the ER3000. LED2, green = On if ER3000 is sending data out, via RS485. LED3, amber = On if ER3000 is receiving data in, via RS485.
LED is on. Check to ensure no jumper is on J3 of the micro (bottom) board if the green LED is on. If not using a Tescom RS485/RS232 converter, refer to Table 5 for proper mode of operation.
Page 57
LED, LED2, is OFF, suspect the wrong node address. • If the error message “Tescom Startup failed. DLL may be in use by another application”, click “OK” and use the ‘Channel Selection’ box to change the comm port. Repeat the above step.
ER3000 is working. Otherwise, “Error” is scrolling, LET IT SCROLL. If unable to resolve the problem, contact your local distributor. A list of Tescom distributors may be found on our website, www.tescom.com, or by contacting the factory. 10.5 Pressure Control Problems If there is a problem with controlling the pressure: •...
10.7 Leak Test The ER3000 can be leak tested using the DOS Tune program or the Windows ER3000(CVI) program. Prior to running the leak test, ensure the following items are done. • ER3000 wired up and communicating to the computer.
Page 60
• Press “spacebar” to toggle Setpoint to 100. • Wait for Feedback to stabilize, which takes approximately 5 seconds. • Press “spacebar” to toggle Setpoint to 50. • Watch Feedback signal for 25 seconds. If feedback decreases, the unit is leaking •...
Fitting Kit (includes ¼”x 1/8” NPT, ¼”x ¼” NPT, and a male tube connector) 80279 Filter 85145 Filter Kit 82575-25 250 mA/24VDC Power Supply 82575-50 500 mA/24VDC Power Supply 85061 RS232 to RS485 converter 82948 USB to RS485 converter 82919 Potentiometer with digital display 60 ER3000 User Manual...
12. MECHANICAL DIMENSIONS OF ER3000 NOTE: DIMENSIONS ARE IN INCHES AND ARE FOR REFERENCE ONLY 12. Mechanical Dimensions of ER3000 61...
Page 63
NOTE: DIMENSIONS ARE IN INCHES AND ARE FOR REFERENCE ONLY 62 ER3000 User Manual...
Page 64
Tescom Corporation Manufacturer’s Address: 12616 Industrial Boulevard Elk River, Minnesota 55330-2491 United States of America European Contact: Marc Lembcke TESCOM EUROPE GMBH & CO. KG An der Trave 23-25 23923 Selmsdorf Germany +49/38823/31-0 declares that the product: Product Name: Electronic Pressure Controller...
Page 65
Emerson Process Management TESCOM 12616 Industrial Boulevard Elk River, Minnesota 55330 USA T +1 800 447 1250 +1 763 241 3238 F +1 763 241 3224 E na.tescom@emerson.com www.TESCOM.com DOPSM1893X012 Rev. 11/09...