SPECIFICATIONS
Enclosure
NEMA 4X / IP65.
To prevent any interference from electromagnetic radiation, use
rigid metal conduit to enclose the wiring entering the ER3000. Two
1/2" NPT wire ports have been provided for this purpose. If unused,
properly seal with a metal plug.
Media
The preferred media is clean, dry instrument grade air or nitrogen.
Use of an in-line 40-micron filter is highly recommended to prevent
damage to the solenoid valves.
Inlet Pressure
Minimum:
Maximum:
Typical:
Note: Response time is affected by inlet pressure.
Environment
Temperature:
Pressure:
Humidity:
Flow Rate
Cv: 0.01
Note: The flow rate can be increased through the use of a booster
regulator.
Power Requirement
Voltage:
Current:
RS485 Communication Interface
Networking:
Cable length:
Baud rate:
Accuracy
Room temp:
Temperature effects: 0.002%/°F of span maximum
Note: Accuracy is based on the user-provided external transducer
when used in external feedback mode.
Outlet pressure + 1 PSIG
120 PSIG
110 PSIG
-20°C to 60°C (dry nitrogen supply gas)
5°C to 60°C (shop air)
28 - 32 inches Hg
To 100% R.H. (non-condensing) @ 0°C to 60°C
24 VDC (22 VDC to 28 VDC)
340mA maximum, 180mA nominal
Up to 32 controllers on one network
4000 ft. maximum
9600
0.1% of span maximum
5