Fluke 433 User Manual page 65

Three phase power quality analyzer
Hide thumbs Also See for 433:
Table of Contents

Advertisement

THRESHOLD
(= TRIGGER)
pretrigger
Figure 15-1. Inrush characteristics and relation with start menu
Use Cursor and Zoom to investigate details of the recorded Trends. Selection of channels
to be displayed is done with the up/down arrow keys. Press function key F1 to assign the
arrow keys to this.
Via the SETUP key and function key F3 - FUNCTION PREF you can set up the default
values of the trigger limits (expected inrush time, maximum current, nominal current,
threshold, hysteresis) and Offset and Span of the Trend display. For detailed information
see Chapter 18, FUNCTION PREFerences.
Available function keys:
Assign up/down arrow keys to select a set of trends for
F1
display.
Cursor on/off.
F2
Assign arrow keys to Cursor or Zoom operation.
F3
Switch between HOLD and RUN of screen update.
F5
Switching from HOLD to RUN invokes a menu to select
immediate (NOW) or TIMED start time which allows you
to define start and duration of the measurement.
MAXIMUM AMPS
DURATION
}
HYSTERESIS
zero
inrush time
rms during inrush
Inrush Trend Display
t
35 s
1
12.3 A
2
12.3 A
3
1.5 A
15
Inrush Currents