RMS Current
Selected Clamp
Sensitivity
0.1 mV/A
1 mV/A
10 mV/A
100 mV/A
1 V/A
Harmonic Currents
Settings
Harmonic selection (n):
Interharmonic selection:
Amplitude Reference
THD
Measurement
Relative Amplitude
Absolute Amplitude
0.1 mV/A
1 mV/A
10 mV/A
100 mV/A
1 V/A
Phase
Frequency
THD
DC relative
absolute
Measurement Range
( CF ≤ 2.8 at full scale)
0.00 ... 20.00 kArms
0 ... 2000 Arms
0.0 ... 200.0 Arms
0.00 ... 20.00 Arms
0.000 ... 2.000 Arms
Range
DC, 1 ... 50
OFF, 1 ... 49
total RMS / fund. RMS
% total / % fundamental
Measurement Range
0.0 ... 100.0 %
0.00 ... 20.00 kArms
0 ... 2000 Arms
0.0 ... 200.0 Arms
0.00 ... 20.00 Arms
0.000 ... 2.000 Arms
-360º ... +360º
0 ... 3500 Hz
0.0 ... 100.0 %
0.0 ... 100.0 %
0.0 ... 100.0 V
Resolution
10 Arms
1 Arms
0.1 Arms
0.01 Arms
0.001 Arms
Additional Information
Grouping: Harmonic Groups according to
IEC61000-4-7
Grouping: Harmonic and Interharmonic Subgroups
according to IEC61000-4-7
Used for Relative Amplitude
based on H1 ... H40
Resolution
0.1 %
10 Arms
1 Arms
0.1 Arms
0.01 Arms
0.001 Arms
1 Hz
0.1 %
0.1 %
0.1 V
Specifications
Electrical Measurements
Accuracy (excl.
Clamp error)
± 1 % of meas ± 5
counts
Accuracy ( excl.
Clamp error )
± 0.1 % ± n x 0.1 %
± 5 % of meas ± 5
counts
± n × 1.5º
± 1 Hz
± 2.5 %
± 1 %
± 5 % of meas ± 10
counts
21
21-7