Fluke 433/434
Users Manual
Measurements
RMS voltage in Transient
Function
Transient voltage
(TTRANS > 10 µs)
Flicker
Settings
Steady Voltage
Tolerance
Minimum Steady Time
Maximum Deviation
Threshold
Measurement
PF5
P1min
Pst
Plt
Dc
DMAX
TDEX
CURRENT MEASUREMENTS
Current Inputs
Nominal input Range
Current Clamp Sensitivity
Input impedance
Bandwidth
Voltage resolution
21-6
Measurement Range
10 ... 1000 Vrms
0 ... ± 6000 Vpeak
Adjustment Range
0.0 ... 10.0 % of Vnom
0.0 ... 10.0 s
0.0 ... 10.0 % of Vnom
Measurement Range
0.00 ... 20.00
0.00 ... 20.00
0.00 ... 20.00
0.00 ... 20.00
0.0 ... ± 100.0 %
0.0 ... ± 100.0 %
0.000 ... 9.999 s
Item
0 - ±5.625 Vpeak
0.1 , 1, 10, 100, 1000 mV/A
variable:
50 k.ohm
>10 kHz
1 mV
Resolution
1 Vrms
1 V
Resolution
0.1 %
0.1 s
0.1 %
Resolution
0.01
0.01
0.01
0.01
0.1 %
0.1 %
10 ms
Specification
0 - 3.97 Vrms sinewave
Accuracy
± 2.5 % of Vnom
± 15 % of meas
Additional
Information
Accuracy
Within ±5 % of tabulated
values according
IEC61000-4-15
± 1 % (if Umeas ≈ Vnom)
± 1 % (if Umeas ≈ Vnom)
20 ms (at F = 50 Hz)
Additional Information