CHAPTER 3: INTERFACES

LED Status Indicators

869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
In 869, the switching device can be configured as Breaker or Contactor ( System > Motor >
Setup). If the switching device is configured as Breaker then the SLD Breaker color is
specified by the LED assigned for BKR 1 Open. If the switching device is configured as
Contactor, then the SLD Contactor color is specified by the LED assigned for Contactor
Open.
If the switching device is first configured as a Breaker (Contactor) and LED X is assigned for
Breaker (Contactor) and later the switching device is changed to Contactor (Breaker) then
user must re-configure LED X for Contactor (Breaker), otherwise previous Breaker
(Contactor) LED configuration will be applied to select the SLD Contactor (Breaker)
Color.
The parameters displayed in the Front panel screen example are as follows.
Parameter
Load Cur
Unbln
Volt (L-L)
Freq
V/ Hz
S:
P:
Q:
PF
Front panel LED details:
Number of LEDs: 17
Programmability: any logic variable, or virtual input
Reset mode: self-reset or latched
The 869 front panel provides two columns of 7 LED indicators each, and 3 LED pushbutton
indicators. The "IN-SERVICE" (LED 1) and the "PICKUP" (LED 4) indicators from the first LED
column are non-programmable LEDs. The bottom 3 LED indicators from the first column,
and the 7 LED indicators from the second LED column are fully programmable. The
indicators "TRIP" (LED 2), and "ALARM" (LED 3), are also programmable, and can be
triggered by either a selection of FlexLogic operand assigned in their own menu, or by the
operation of any protection, control or monitoring element with function selected as Trip,
Alarm, or Latched Alarm.
The RESET key is used to reset any latched LED indicator or Target Message once the
condition has been cleared (latched conditions can also be reset via the RESETTING menu).
Figure 3-8: Typical LED Indicator Panel
Input for the value
Metering\Generator\General\Load Current
Metering\Generator\General\Unbalance Current
Metering\Ph VT Bnk1-J2\J2 V AVG L-L
Metering\Frequency 1-J\J2-3VT Frequency
Metering\Volts per Hertz\Volts Per Hertz 1
Metering\Power 1\Pwr1 Apparent
Metering\Power 1\Pwr1 Real
Metering\Power 1\Pwr1 Reactive
Metering\Power 1\Pwr1 PF
STOPPED
IN SERVICE
TRIP
STARTING
ALARM
RUNNING
PICK UP
OVERLOAD
START INHIBIT
TEST MODE
GROUND FAULT
MESSAGE
LOCAL MODE
HOT RTD
FRONT CONTROL PANEL INTERFACE
3–7