GE MI-869 Instruction Manual page 296

Motor protection system/motor protection, control and management
Table of Contents

Advertisement

PROTECTION
MULTIPLIER
CURRENT (I/I
(TDM)
1.5
10.0
11.552
IAC SHORT INVERSE
0.5
0.072
1.0
0.143
2.0
0.286
4.0
0.573
6.0
0.859
8.0
1.145
10.0
1.431
2
Table 4-28: I
T CURVE TRIP TIMES (IN SECONDS)
MULTIPLIER
CURRENT (I/I
(TDM)
1.5
0.01
0.44
0.10
4.44
1.00
44.44
10.00
444.44
100.00
4444.44
600.00
26666.7
4–178
)
pickup
2.0
3.0
4.0
7.494
5.320
4.426
0.047
0.035
0.031
0.095
0.070
0.061
0.190
0.140
0.123
0.379
0.279
0.245
0.569
0.419
0.368
0.759
0.559
0.490
0.948
0.699
0.613
2
I
T CURVES
2
The curves for the I
t are derived from the formula:
Where:
T = operate time (in seconds)
TDM = Multiplier setting
I = input current
I
= Pickup Current setting
pickup
T
= reset time in seconds (assuming energy capacity is 100% and RESET is
RESET
"Timed")
)
pickup
2.0
3.0
4.0
0.25
0.11
0.06
2.50
1.11
0.63
25.00
11.11
6.25
250.00
111.11
62.50
2500.00
1111.1
625.00
15000.0
6666.7
3750.0
4
I
T CURVES
4
The curves for the I
t are derived from the formula:
Where:
T = operate time (in seconds)
TDM = Multiplier setting
I = input current
I
= Pickup Current setting
pickup
5.0
6.0
7.0
3.922
3.597
3.369
0.028
0.027
0.026
0.057
0.054
0.052
0.114
0.108
0.105
0.228
0.217
0.210
0.341
0.325
0.314
0.455
0.434
0.419
0.569
0.542
0.524
5.0
6.0
7.0
0.04
0.03
0.02
0.40
0.28
0.20
4.00
2.78
2.04
40.00
27.78
20.41
400.00
277.78
204.08
2400.0
1666.7
1224.5
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: SETPOINTS
8.0
9.0
10.0
3.201
3.072
2.969
0.026
0.025
0.025
0.051
0.050
0.049
0.102
0.100
0.099
0.204
0.200
0.197
0.307
0.301
0.296
0.409
0.401
0.394
0.511
0.501
0.493
8.0
9.0
10.0
0.02
0.01
0.01
0.16
0.12
0.10
1.56
1.23
1.00
15.63
123.5
10.00
156.25
123.46
100.00
937.50
740.74
600.00

Advertisement

Table of Contents
loading

This manual is also suitable for:

869