SPECIFICATIONS

Monitoring

1–18
BREAKER ARCING CURRENT
Mode:........................................................................ 3-pole
Principle: ................................................................. accumulates breaker duty (I
Initiation:................................................................. any operand
Alarm Threshold:................................................. 0 to 50000 kA2-cycle in steps of 1 kA2-cycle
Timer Accuracy: .................................................. ± 3% of delay setting or ± ¼ cycle (whichever is greater) from
BREAKER FAILURE
Mode:........................................................................ 3-pole
Current Supervision:.......................................... phase and neutral current (fundamental phasor magnitude)
Current Supervision Pickup:........................... 0.050 to 30.000 x CT in steps of 0.001 x CT
Current Supervision Dropout: ....................... 97 to 98% of pickup
Current Supervision Accuracy:..................... For 0.1 to 2.0 x CT: ± 0.5% of reading or ± 0.4% of rated
Time Delay:............................................................ 0.000 to 6000.000 s in steps of 0.001 s
Timer Accuracy: .................................................. ± 3% of delay setting or ± ¼ cycle (whichever is greater) from
Reset Time: ............................................................ < 10 ms typical at 2 x Pickup at 60 Hz
BREAKER HEALTH
Timer Accuracy: .................................................. ± 3% of delay setting or ± 1 cycle (whichever is greater) from
BROKEN ROTOR BAR
Operating Parameter: ...................................... Fundamental Phasor Magnitude
Pickup Level: ......................................................... -60db to -12db in steps of -1dB
Dropout Level: ...................................................... 97 to 98% of Pickup
CLOSE CIRCUIT MONITOR (CCM)
Applicable Voltage: ............................................ 20 to 250 VDC
Trickle Current:.....................................................1 to 2.5 mA
Timing Accuracy:................................................ ± 3 % or ± 4 ms, whichever is greater
DEMAND
Measured Values: ............................................... Phase A/B/C present and maximum current
Measurement Type:........................................... Thermal Exponential, 90% response time (programmed): 5,
Current Pickup Level: ........................................ 10 to 10000 in steps of 1 A
Dropout Level: ...................................................... 96-98% of Pickup level
Level Accuracy:.................................................... ± 2%
FAULT REPORTS
Number of Reports: ........................................... 15
Captured Data: .................................................... Pre-fault and fault phasors for all CT and VT banks, pre-fault
HARMONIC DETECTION
Operating Parameter: ...................................... Current 2
Timer Accuracy: .................................................. Harmonics: ±3% of delay setting or ±1/4 cycle (whichever is
2
t) during fault
pickup to operate
(whichever is greater),
For > 2.0 x CT: ± 1.5% of reading
pickup to operate
< 12 ms typical at 2 x Pickup at 50 Hz
pickup to operate
10, 15, 20, 30 minutes
Block Interval / Rolling Demand, time interval (programmed):
5, 10, 15, 20, 30 minutes
and fault trigger operands, user-programmable analog
channels 1 to 32
nd
rd
th
th
, 3
, 4
, 5
harmonic or THD per phase
greater) from pickup to operate
THD: ±3% of delay setting or ±3 cycles (whichever is greater)
from pickup to operate
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL