GE MI-869 Instruction Manual page 374

Motor protection system/motor protection, control and management
Table of Contents

Advertisement

PROTECTION
FASTPATH:
4–256
PICKUP
Range: 0.10 to 15.00 Hz/sec in steps of 0.01 Hz/sec
Default: 0.50 Hz/sec
The setting specifies an intended Pickup threshold.
For applications monitoring a decreasing trend, set TREND to "Decreasing" and specify
the Pickup threshold accordingly. The operating condition is: -df/dt > PKP.
For applications monitoring an increasing trend, set TREND to "Increasing" and specify
the pickup threshold accordingly. The operating condition is: df/dt > PKP.
For applications monitoring rate of change of frequency in any direction, set TREND to
"Bi-Directional" and specify the Pickup threshold accordingly. The operating condition
can be either of the above two conditions.
PICKUP DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 2.000 s
This setting provides a definite Pickup time delay. Instantaneous operation is selected by
a Pickup time delay setting of 0.000 s.
MINIMUM FREQUENCY
Range: 20.00 to 80.00 Hz in steps of 0.01 Hz
Default: 45.00 Hz
The setting defines the minimum frequency level required for operation of the element.
The setting may be used to effectively block the feature based on frequency. For
example, if the intent is to monitor an increasing trend but only if the frequency is
already above certain level, this setting is set to the required frequency level.
MAXIMUM FREQUENCY
Range: 20.00 to 80.00 Hz in steps of 0.01 Hz
Default: 65.00 Hz
The setting defines the maximum frequency level required for operation of the element.
The setting may be used to effectively block the feature based on frequency. For
example, if the intent is to monitor a decreasing trend but only if the frequency is already
below a certain level (such as for load shedding), this setting is set to the required
frequency level.
MINIMUM VOLTAGE
Range: 0.000 to 1.250 x VT in steps of 0.001 x VT
Default: 0.700 x VT
The setting defines the minimum voltage level required for operation of the element. The
supervising function responds to the positive-sequence voltage. Overvoltage
supervision is used to prevent operation under specific system conditions such as faults.
If the 3-phase VT uses a delta connection and FREQUENCY INPUT is set to J2-3VT, the
positive sequence voltage is used as the supervision voltage. In such condition, the true
supervision level is internally changed to 1/sqrt(3) of the user setting since the base of VT
here is the phase-phase voltage.
MINIMUM CURRENT
Range: 0.000 to 30.000 x CT in steps of 0.001 x CT
Default: 0.200 x CT
This setting defines the minimum current level required for operation of the element. The
supervising function responds to the positive-sequence current. Typical application
includes load shedding. Set the Pickup threshold to zero if no overcurrent supervision is
required. The setting of zero suspends the current supervision.
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL