GE MI-869 Instruction Manual page 446

Motor protection system/motor protection, control and management
Table of Contents

Advertisement

CONTROL
4–328
working properly or defaulted to the factory setting, LO time will remain unchanged and
prevent the motor from starting until LO time becomes zero or the Emergency Restart is
asserted.
Path:
Setpoints > Control > Motor Starting > Start Supervision > Time Between Starts
Function
Range: Disabled, Enabled
Default: Disabled
Minimum Time
Range: 1 to 600 min in steps of 1 min
Default: 10 min
Sets time amount of time following a start before a start control is permitted to prevent
restart attempts in quick succession (jogging).
Events
Range: Disabled, Enabled
Default: Enabled
Targets
Range: Disabled, Self-reset, Latched
Default: Latched
Figure 4-131: Time Between Starts logic diagram
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: SETPOINTS