3 Functions
3.5.6

Series commissioning

The parameter set can be read-out (upread) from the drive converter via the serial
interface and saved on the hard disk / floppy disk or in a non-volatile memory (e.g.
EEPROM) using the following
PC Tools (e.g. STARTER, DriveMonitor) or the
Operator panel AOP
(please refer to Fig. 3-25).
The interfaces of the drive inverter with USS protocol and the fieldbus interfaces
(e.g. PROFIBUS) which can be used to transfer parameters, can be used as serial
interface.
AOP
DriveMonitor
STARTER
Parameter transmission from different
sources via download
Fig. 3-25
If there is already an appropriate parameter set for the drive, which, for example,
was created by either upreading or by programming offline, then this can be
downloaded into the drive inverter. This means that it is possible to transfer the
parameter set from drive inverter A to drive inverter B which, for identical
applications (e.g. series machines, group drives) allows data to be copied and
therefore in turn fast commissioning.
96
3)*
1)
USS on BOP link
2)*
USS on COM link
4)*
CB on COM link
(PROFIBUS)
2)*
4)*
5)*
Upread / download using AOP and PC Tools
(RS232)
(RS485)
CB
*
Option is absolutely required for the
connection
1) Option: Operator panel door mounting kit
for single inverter control
2) Option: PC to inverter connection kit
3) Option: AOP door mounting kit
for multiple inverter control (USS)
4) Option: RS232-RS485 Converter
5) With PROFIBUS:
SIMATIC NET
With CANopen or DeviceNet:
see user organisation
MICROMASTER 440
Issue 10/03
MM4
Operating Instructions
6SE6400-5AW00-0BP0