Fig. 3-11 Copying From Dds - Siemens MICROMASTER 440 Operating Instructions Manual

Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Issue 10/03
The drive data set (DDS) contains various setting parameters which are of
significance for the open-loop and closed-loop control of a drive:
Motor and encoder data, e.g.:
♦ Select motor type
♦ Rated motor voltage
♦ Main inductance
♦ Select encoder type
Various closed-loop control parameters, e.g.:
♦ Fixed frequency 1
♦ Min. frequency
♦ Ramp-up time
♦ Control mode
The parameters, combined in a drive data set, are designated with an [x] in the
parameter list in the index field:
Pxxxx[0] : 1
Pxxxx[1] : 2
Pxxxx[2] : 3
NOTE
A complete list of all of the DDS parameters can be taken from the parameter list.
It is possible to parameterize several drive data sets. This makes it easier to toggle
between various drive configurations (control mode, control data, motors) by
selecting the appropriate drive data set.
Just like the command data sets, it is possible to copy drive data sets within the
MICROMASTER. P0819 is used to control the copy operation as follows:
1. P0819[0] = Number of the drive data set which is to be copied (source)
2. P0819[1] = Number of the drive data set into which data is to be copied
(target)
3. P0819[2] = 1 → Copying is started
Fig. 3-11
MICROMASTER 440
Operating Instructions
6SE6400-5AW00-0BP0
P0300
P0304
P0360
P0400
P1001
P1080
P1120
P1300
st
drive data set (DDS)
nd
drive data set (DDS)
rd
drive data set (DDS)
Copying has been completed, if P0819[2] = 0.
P0819[0] = 0
1. DDS
P0819[1] = 2
3. DDS
P0819[2] = 1
Start copy
Copying from DDS
[0]
[1]
P0005
P0291
P0300
P0304
P0305
. .
. .
. .
. .
. .
. .
.
.
.
P2484
P2487
P2488
2. DDS 3. DDS
1. DDS
3 Functions
[2]
. .
. .
.
63

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents