Issue 10/03
3.15

Automatic restart

Parameter range:
Warnings
Faults
Function chart number:
After a power failure (F0003 "Undervoltage"), the "Automatic restart" function
(enabled using P1210) automatically powers-up the drive inverter again. Any faults
are automatically acknowledged by the drive inverter.
When it comes to power failures (line supply failure), then a differentiation is made
between the following conditions:
Line undervoltage (brownout)
"Line undervoltage" is a situation where the line supply is interrupted and returns
before (if installed) the BOP display has gone dark (this is an extremely short line
supply interruption where the DC link hasn't completely collapsed).
Line failure (blackout)
"Line failure" is a situation where the display has gone dark (this represents a
longer line supply interruption where the DC link has completely collapsed) before
the line supply returns.
The automatic restart function P1210 is shown in the following diagram (refer to
Fig. 3-60) as a function of external states / events.
P1210
0
1
Fault acknowl.
Fault acknowl.
2
Fault acknowl.
3
Fault acknowl.
4
Fault acknowl.
5
Fault acknowl.
6
Fig. 3-60
MICROMASTER 440
Operating Instructions
6SE6400-5AW00-0BP0
P1210
P1211
A0571
F0035
-
ON always active
Fault F0003 for
Blackout
Brownout
+
restart
Fault acknowl.
+
+
restart
restart
Fault acknowl.
+
+
restart
restart
+
restart
Fault acknowl.
+
+
restart
restart
Automatic restarts
All other faults for
Blackout
Brownout
Fault acknowl.
Fault acknowl.
+
+
restart
restart
Fault acknowl.
+
restart
Fault acknowl.
Fault acknowl.
+
+
restart
restart
3 Functions
ON in the
no-voltage state
All faults + F0003
Fault acknowl.
Fault acknowl.
+
restart
Fault acknowl.
+
restart
Fault acknowl.
+
restart
145