Siemens MICROMASTER 440 Operating Instructions Manual page 88

Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

3 Functions
Example
P0700=1 P0700=2
Function of digital input 1
P0701 = 1
Terminal 5
Function of digital input 2
P0702=12
Terminal 6
12
Function of digital input 3
P0703 = 9
Terminal 7
Function of digital input 4
P0704=15
Terminal 8
15
Function of digital input 5
P0705=15
Terminal 16
15
Function of digital input 6
P0706=15
Terminal 17
15
Function of digital input 7
P0707 = 0
Terminal 3
Function of digital input 8
P0708 = 0
Terminal 10
Debounce time for digital inputs
P0724 = 3
Defines the debounce time (filtering time) used for digital inputs.
PNP / NPN digital inputs
P0725 = 1
Switches between active high (PNP) and active low (NPN).
This applies for all digital inputs simultaneously.
BI: Function of digital output 1
P0731 = 52:3
Defines the source for digital output 1.
Terminal 18(NC), 19(NO), 20(COM)
52.3 Drive fault active
BI: Function of digital output 2
P0732 = 52:7
Defines the source for digital output 2.
Terminal 21(NO), 22(COM)
52.7 Drive warning active
BI: Function of digital output 3
P0733 = 0:0
Defines the source for digital output 3.
Terminal 23(NC), 24(NO), 25(COM)
0.0
88
1
ON / OFF1
Reversing
9
Fault acknowledge
Fixed setpoint
(direct selection)
Fixed setpoint
(direct selection)
Fixed setpoint
(direct selection)
0
Digital input disabled
0
Digital input disabled
0
No debounce time
1
2.5 ms debounce time
2
8.2 ms debounce time
3
12.3 ms debounce time
0
NPN mode ==> low active
1
PNP mode ==> high active
Digital output disabled
0
Digital input inhibited
1
ON / OFF1
2
ON + reverse / OFF1
3
OFF2 – coast to standstill
4
OFF3 – quick ramp-down
9
Fault acknowledge
10
JOG right
11
JOG left
12
Reverse
13
MOP up
(increase frequency)
14
MOP down
(decrease frequency)
15
Fixed setpoint (direct selection)
16
Fixed setpoint
(direction selection + ON)
17
Fixed setpoint (BCD-coded + ON)
25
Enable DC braking
29
External trip
33
Disable additional freq. setpoint
99
Enable BICO parameterization
ON > 3.9 V, OFF < 1.7 V
DIN7
DIN8
1
2
3
4
Frequent settings:
0.0
Digital output disabled
52.0 Drive ready
52.1 Drive ready to run
52.2 Drive running
52.3 Drive fault active
52.4 OFF2 active
52.5 OFF3 active
52.6 Switch-on inhibit active
52.7 Drive warning active
52.8 Deviation, setpoint/actual
value
52.9 PZD control
(Process Data Control)
52.A Max. frequency reached
MICROMASTER 440
Issue 10/03
1
2
10
11
Operating Instructions
6SE6400-5AW00-0BP0