Power Module Protection; Table 3-22 General Protection Of The Power Components; General Overload Monitoring - Siemens MICROMASTER 440 Operating Instructions Manual

Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

3 Functions
3.21

Power module protection

3.21.1

General overload monitoring

Parameter range:
Warnings
Faults
Function chart number:
Just the same as for motor protection, MICROMASTER provides extensive
protection for the power components. This protection concept is also sub-divided
into 2 levels:
Warning and response
Fault and shutdown
Using this concept, a high utilization of the power module components can be
achieved without the drive inverter being immediately shut down. The power
module components are monitored as follows:
Table 3-22
Overcurrent / short circuit
DC link overvoltage
DC link undervoltage
Line phase failure detection
(refer to P0291)
The monitoring thresholds for the righthand column in the table above are
permanently saved in the drive inverter and cannot be changed by the user. On the
other hand, the threshold levels for the "Warning and response" column can be
modified by the user to optimize the system. These values have default settings so
that the "Fault and shutdown" thresholds do not respond.
162
P0640, r0067, r1242, P0210
A0501, A0502, A0503
F0001, F0002, F0003, F0020
-
General protection of the power components
Warning and response
(refer to Section 3.22.1.2)
Current controller for SLVC /
Imax controller for V/f
A0501
r0056 bit 09
r0056 bit 13
VC
---
r0056 bit 09
r1407 bit 08
r1407 bit 09
Vdc_max controller
A0502
(refer to Section 3.17.1)
Vdc_min controller
A0503
(refer to Section 3.17.2)
---
MICROMASTER 440
Issue 10/03
Fault and shutdown
F0001
F0002
F0003
F0020
Operating Instructions
6SE6400-5AW00-0BP0