Positioning Down Ramp; Table 3-19 Dc Link Undervoltage - Shutdown Threshold - Siemens MICROMASTER 440 Operating Instructions Manual

Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

3 Functions
NOTE
When the minimum DC link voltage V
"Undervoltage" is output and the drive inverter is shut down. The shutdown
threshold V
Table 3-19
Drive inverter type / line supply voltage
3.18

Positioning down ramp

Parameter range:
Warnings
Faults
Function chart number:
The positioning down ramp (enabled using P0500) can be used for applications
where it is necessary that a residual distance is moved-through up to the stop
dependent on an external event (e.g. BERO switch). In this case, MICROMASTER
440 generates a continuous braking ramp by selecting OFF1 depending on the
actual load speed / velocity. The drive is then stopped/positioned along this braking
ramp (refer to Fig. 3-64).
f
OFF1
Fig. 3-64
In this case, the remaining distance P2488 moved through must be entered,
referred to the load. In order to carry-out the residual distance calculation on the
load side, the mechanical arrangement of the axis (gearbox ratio, linear or rotary
axis) must be appropriately parameterized (refer to Fig. 3-65).
152
depends on the drive inverter type / line supply voltage.
DC_min
DC link undervoltage – shutdown threshold
1-ph. 200 V – 240 V AC ± 10 %
3-ph. 200 V – 240 V AC± 10 %
3-ph. 380 V – 480 V AC ± 10 %
3-ph. 500 V – 600 V AC ± 10 %
P0500
P2480 – r2489
-
-
-
Motor
f
OFF1

Positioning down ramp

is fallen below, fault F0003
DC_min
Shutdown threshold V
215 V
215 V
430 V
530 V
Gear
=
=
s
P2488
t
t
P2488
MICROMASTER 440
Issue 10/03
DC_min
1
.
f
.
t
OFF1
P2488
2
Operating Instructions
6SE6400-5AW00-0BP0