SET EXERCISE TIME

To set the exercise time, the engine control module switch
must be in the ATS mode. Decide on the desired day and time
to exercise the generator. Press the exercise switch to ON. The
generator will start and run for 15 minutes and then shut off.
The exercise time is now set. The generator will begin the next
exercise period exactly 168 hours from when the exercise switch
was pressed to the ON position.
If you choose to change the current exercise time setting, choose
the new day and time and cycle the exercise switch from off to
on and it will begin the cycle again. (Figure 4)
The exercise time will have to be reset if:
The battery was disconnected from the generator
The switch was moved to the OFF position for
maintenance
HOUR METER
The generator is equipped with an hour meter that will display
the generator actual run and exercise times.
ENGINE CONTROL MODULE
The engine control module contains the ATS/OFF/Manual mode
switch and the LEDs that indicate if a generator operation is
being performed or if there is an active alarm. (Figure 5)
If the exterior fault code indicator light is on, open the enclosure
to view the engine control module. Determine what the fault code
is and remedy the situation or have the generator serviced by an
authorized Service Dealer or contact Champion Customer Service
at 1-877-338-0999.
RESET FAULT CODE(S)
There is also an exterior fault code indicator light located on the
back of the enclosure. This should be checked weekly to make
sure there are no active fault codes.
The fault code(s) can be reset by placing the Engine Control
Module (Figure 5) in the OFF position. This will reset fault LED,
however if a fault code(s) re-occurs it must be addressed.
© 2015 Champion Power Equipment
GENERAL INFORMATION
Exercise / Exercice /
Ejercicio
Batterie faible
Low battery /
Batería baja
Hz over/under / Hz plus / sous
Hz Más / Menos
High engine temperature
Surchauffe moteur
Alta temperatura del motor
Low oil / Huile basse
Baja de aceite
Over crank
Surdémarrage
Sobre manivela
Run / Marche
Funcionar
Power / Alimentation
Potencia
Figure 5
MODE SWITCH
ATS – This position allows for fully automatic operation. If
utility power is lost, the generator will automatically start
up. It also allows the generator to automatically perform
the exercise period.
OFF – This position shuts down the engine and prevents
automatic operation of the generator.
Manual – This position allows manual starting of the
engine. Load transfer from the generator output does not
occur unless the utility power is lost.
EXERCISER LED
The green LED will be lit when the generator is performing the
excercise period. When the exercise period has completed, the
LED will turn off.
LOW BATTERY LED
The yellow LED will be lit if the battery voltage fell below 21.0
volts for at least one minute while the engine was running. If
battery voltage rises above 21.1 volts, the LED will turn off.
Battery voltage is not monitored when cranking the engine.