6. Using Macro Mode and Getting a Quick Start

A special Macro programming mode is available with the Vacon 50X series of AC drives. The Macro pro-
gramming mode allows you to customize quickly the most common parameters for your application in
the Level 1 group. Macro mode provides special parameters for activating modes of operation by macros,
program sequencer, or serial communications.
Parameters important to the drive's operation are also included in Macro mode. Although these param-
eters are also available with standard programming, the Macro mode allows you to easily configure the
drive with essential parameters.
Macros configure what advanced functions will be active in the drive. A macro can also change the default
or visibility of a parameter within the programming levels. Parameter 490 (Appl Macro) configures what
macro will be active in the drive. Parameter 491 (Seq Appl) configures the visibility of sequencer param-
eters and the time base of the sequencer. Parameter 492 (SIO Visible) configures whether or not SIO pa-
rameters are visible. (See page 50.)

6.1 Entering Macro Mode

To enter the Macro mode, press and hold the PROGram key for more than three seconds. The drive then
enters Macro mode and displays "Hold PROG for Macro Mode." Following is a list of the different macros
available and their features. A description of parameters used in Macro mode begins on page 49.

6.2 Description of Parameters Used in Macro Mode

Parameters 490, 491, and 492 are used only in the Macro mode. Parameters 509, 510, 511, 801, and 810
are used in both Macro and Level 2 programming. Vacon 50X parameters are described in "Vacon 50X Pa-
rameters" on page 59 of this manual.
6
using macro mode and getting a quick start
Factory
The Factory macro provides a simple way to restore the factory default
parameter listings.
Fan
The Fan macro provides a basic set-up for Fan applications. Parameters
such as the V/Hz curve and terminal strip operation are available in Level
1 programming.
Fan w/ PI
The Fan w/ PI macro allows for a simple set-up for Fan applications re-
quiring process control. Parameters such as the V/Hz curve, terminal
strip operation, and PI configuration parameters are available in Level 1
programming.
Pump
The Pump macro provides a basic set-up for Pump applications. Param-
eters such as the V/Hz curve and terminal strip operation are available
in Level 1 programming.
Pump w/ PI
The Pump w/ PI macro allows for a simple set-up for Pump applications
requiring process control. Parameters such as the V/Hz curve, terminal
strip operation, and PI configuration parameters are available in Level 1
programming.
Vector
The Vector macro activates the sensorless vector control algorithm.
When an operation requires low speed and high torque, this macro
should be activated.