Mitsubishi Electric FR-PU07 Instruction Manual page 42

Parameter unit
Hide thumbs Also See for FR-PU07:
Table of Contents

Advertisement

FUNCTIONS
Description
Enter "50" and press the WRITE-key.
50 Hz is set.
Press the FWD-key.
Forward rotation is performed at 50 Hz.
You need not connect the motor.
Using the Cursor-keys ▲/▼, adjust the meter pointer to a predeter-
mined position.
The meter pointer moves.
(It takes a long time before the pointer moves.)
Press the WRITE-key.
Calibration is complete.
Press the MON-key to return to the
main monitor screen.
32
When calibrating output current
Display
To output the output current or another item which cannot easily
901 AM Tune
achieve a 100% value if operation is performed, adjust the ref-
Run Inverter
erence voltage output, then select any of the choices displayed.
50Hz
PU
Description
Press the PU-key.
901 AM Tune
The frequency setting screen appears
Mntrf
50.00Hz
to switch to PU operation mode.
<WRITE>PU
Press the PrSET-key.
The parameter unit is put in the param-
eter setting mode.
901 AM Tune
Completed!
Enter "158" and press the READ-key.
Monitor
The current Pr. 158 setting appears.
READ:
List
50.00
Enter "21" and press the WRITE-key.
Hz
The setting of reference voltage output
STF FWD
PU
is complete.
Press the PrSET-key.
The parameter unit is put in the param-
eter setting mode.
Display
Freq Set
SET
0.00Hz
0~400Hz
SETTING MODE
0~9:Ser Pr.NO.
Select Oper
158 AM set
1
158 AM set
21
Completed
SETTING MODE
0~9:Ser Pr.NO.
Select Oper