Func.
Name
Code
B134
Decel. overvolt.
suppress integral
time
b145
GS input mode
b146
Delay time of
*4
release operation
b147
Special monitor
*4
display
cancellation
b148
Special monitor
*4
display re-display
time
b150
Display
ex.operator
connected
b160
1st parameter of
Dual Monitor
b161
2nd parameter of
Dual Monitor
b163
Frequency set in
monitoring
b164
Automatic return
to the initial
display
b165
Ex. operator com.
loss action
b166
Data Read/Write
select
b171
Inverter mode
selection
b180
Initialization
trigger
"b" Function
Description
Integration time when b130=01. Range is: 0.0
to 150.0
Two option codes:
00...No trip (Hardware shutoff only)
01...Trip (E37)
02
*4
...Trip (E98/E99) or hardware shutoff (-S--)
03
*4
...Trip (E99) or hardware shutoff (-S--)
04
*4
...No trip, Hardware shutoff (-S--)
05
*4
...Trip (E99) or
hardware shutoff (F01/F02/F10/F20/-S--)
06
*4
...No trip,
hardware shutoff (F01/F02/F10/F20/-S--)
Valid only when b145 = 05.
Range is: 0.00 to 2.00 sec
Two option codes:
00...cancellation disable
01...cancellation enable
Set range: 1. to 30. sec
When an external operator is connected via
RS-422 port, the built-in display is locked and
shows only one "d" parameter configured in:
d001 to d030
Set any two "d" parameters in b160 and b161,
then they can be monitored in d050. The two
parameters are switched by up/down keys.
Set range: d001 to d030
Two option codes:
00...Freq. set disabled
01...Freq. set enabled
10 min. after the last key operation, display
returns to the initial parameter set by b038. Two
option codes:
00...Disable
01...Enable
Five option codes:
00...Trip
01...Trip after deceleration to a stop
02...Ignore
03...Coasting (FRS)
04...Decelerates to a stop
00... Read/Write OK
01... Protected
Three option codes:
00...No function
01...Std. IM (Induction Motor)
02...High frequency induction motor
03...PM (Permanent Magnet Motor)
This is to perform initialization by parameter
input with b084, b085 and b094. Two option
codes:
00...Initialization disable
01...Perform initialization
72
Defaults
A
B
Initial data
1.0
00
0.00
01
30.
001
001
002
00
00
02
00
00
00
Units
s
s
s