Func.
Name
Code
B061
Minimum-limit
level of window
comparator (O)
B062
Hysteresis width
of window
comparator (O)
B063
Maximum-limit
level of window
comparator (OI)
B064
Minimum-limit
level of window
comparator (OI)
b065
Hysteresis width
of window
comparator (OI)
b070
Operation level at
O disconnection
b071
Operation level at
OI disconnection
b075
Ambient
temperature
setting
B078
Watt-hour
clearance
b079
Watt-hour display
gain
B082
Start frequency
B083
Carrier frequency
B084
Initialization mode
(parameters or trip
history)
B085
Country for
initialization
B086
Frequency scaling
conversion factor
B087
STOP key enable
B088
Restart mode
after FRS
"b" Function
Description
Set range, 0 to {Max.-limit level (b060) -
hysteresis width (b062)x2} % (Maximum of 0%)
Set range, 0 to {Max.-limit level (b060) -
Min.-limit level (b061)}/2 % (Maximum of 10%)
Set range, {Min.-limit level (b064 + hysteresis
width (b065)x2} to 100 %
(Minimum of 0%)
Set range, 0 to {Max.-limit level (b063) -
hysteresis width (b065)x2} % (Maximum of 0%)
Set range, 0 to {Max.-limit level (b063) -
Min.-limit level (b064)}/2 % (Maximum of 10%)
Set range, 0. to 100.%, or "no" (ignore)
Set range, 0. to 100.%, or "no" (ignore)
Set range is,
-10 to 50 °C
Two option codes:
00...OFF
01...ON (press STR then clear)
Set range is,
1. to 1000.
Sets the starting frequency for the inverter
output, range is 0.10 to 9.99 Hz
Sets the PWM carrier (internal switching
frequency), range is 2.0 to 15.0 kHz
Select initialized data, five option codes:
00...Initialization disabled
01...Clears Trip history
02...Initializes all Parameters
03...Clears Trip history and initializes all
parameters
04...Clears Trip history and initializes all
parameters and EzSQ program
01...Mode 1
Specify a constant to scale the displayed
frequency for D007 monitor, range is 0.01 to
99.99
Select whether the STOP key on the keypad is
enabled, three option codes:
00...Enabled
01...Disabled always
02...Disabled for stop
Selects how the inverter resumes operation
when free-run stop (FRS) is cancelled, three
options:
00...Restart from 0Hz
01...Restart from frequency detected from real
speed of motor (freq. matching)
02...Restart from frequency detected from real
speed of motor (active freq. matching)
69
Defaults
A
B
Initial data
0.
0.
100.
0.
0.
no
no
40
00
1.
0.50
10.0
00
01
1.00
00
00
Units
%
%
%
%
%
°C
Hz
kHz

Hide quick links:

Advertisement

Table of Contents
loading