Func.
Name
Code
A095
Acc1 to Acc2 frequency
transition point
A295
Acc1 to Acc2 frequency
transition point, 2
motor
A096
Dec1 to Dec2 frequency
transition point
A296
Dec1 to Dec2 frequency
transition point, 2
motor
A097
Acceleration curve
selection
A098
Deceleration curve
selection
A101
[OI] input active range
start frequency
A102
[OI] input active range
end frequency
A103
[OI] input active range
start current
A104
[OI] input active range
end current
A105
[OI] input start
frequency select
a131
Acceleration curve
constant
a132
Deceleration curve
constant
"A" Function
Description
Output frequency at which
Accel1 switches to Accel2,
range is 0.00 to
*1
400.0(580.0)
nd
Output frequency at which
Decel1 switches to Decel2,
range is 0.00 to
*1
400.0(580.0)
nd
Set the characteristic curve of
Acc1 and Acc2, five options:
00...linear
01...S-curve
02...U-curve
03...Inverse U-curve
04...EL S-curve
Set the characteristic curve of
Dec1 and Dec2, options are
same as above (a097)
The output frequency
corresponding to the analog
input range starting point,
range is 0.00 to
*1
400.0(580.0)
The output frequency
corresponding to the current
input range ending point,
range is 0.00 to
*1
400.0(580.0)
The starting point (offset) for
the current input range,
range is 0. to 100.%
The ending point (offset) for
the current input range,
range is 0. to 100.%
Two options; select codes:
00...Use offset (A101 value)
01...Use 0Hz
Range is 01 to 10.
Range is 01 to 10.
A
Hz
Hz
Hz
Hz
62
Defaults
B
Initial data
0.00
0.00
0.00
0.00
01
01
0.00
0.00
20.
100.
00
02
02
Units
Hz
Hz
Hz
Hz
Hz
Hz
%
%

Hide quick links: