Terminal Name
O
H
SP, SN
AL0, AL1, AL2 *3
Note 1:
The two terminals [L] are electrically connected together inside the inverter.
Note 2:
We recommend using [L] logic GND (to the right) for logic input circuits and [L]
analog GND (to the left) for analog I/O circuits.
Note 3:
Refer to page 42 for details of trip signals.
Note 4:
Refer to page 96, "Functional safety" for details
Wiring sample of control logic terminal (Source logic)
SN
7/EB
SP
EO
EA
Note:
If relay is connected to intelligent output, install a diode across the relay coil
(reverse-biased) in order to suppress the turn-off spike.
Caution for intelligent terminals setting
Please avoid conducting below procedure, because if you follow procedure describe below, the
inverter setting will be initialized.
1) Turning on power while [Intelligent input terminal 1/2/3 are ON] and [Intelligent input
terminal 4/5/6/7 are OFF].
2) After 1)'s condition, turning off power.
After 2)'s condition, turning on power while [Intelligent input terminal 2/3/4 are ON]
3)
and [Intelligent input terminal 1/5/6/7 are OFF].
Sink/source logic of intelligent input terminals
Description
Analog voltage input
+10V analog reference
Serial communication terminal
Relay common contact
6
5/PTC 4/GS2 3/GS1
H
O
OI
Variable resistor
for freq. setting
(1kΩ-2kΩ)
0 to 9.8 VDC range, 10 VDC nominal,
input impedance 10 kΩ
10VDC nominal, 10mA max.
For RS485 Modbus communication.
250VAC,
250VAC,
100VAC,
30VDC,
30VDC,
5VDC, 100mA min.
Jumper wire
(source logic)
1
L
2
L
AM
CM2
Freq. meter
27
Ratings
2.5A (R load) max.
0.2A (I load, P.F.=0.4) max.
10mA min.
3.0A (R load) max.
0.7A (I load, P.F.=0.4) max.
PLC
P24
12
11/EDM
RY
RY