Mantel Requirements - kozy heat BAYPORT-41 LOG Installation And Operation Manual

Direct vent gas fireplace
Hide thumbs Also See for BAYPORT-41 LOG:
Table of Contents

Advertisement

4.2 Mantel Requirements

*NON-COMBUSTIBLE ZONE: 48 in (1219mm) MINIMUM WHEN VENTING FROM REAR VENT EXITS
**NON-COMBUSTIBLE ZONE: 54 in (1372mm) MINIMUM FOR TOP VENTING MINIMUM HORIZONTAL VENT
TERMINATIONS
USE THE DIMENSION THAT PROVIDES THE MOST HEIGHT CLEARANCE TO COMBUSTIBLE CONSTRUCTION
FOR YOUR VENTING INSTALLATION. 1
TOP SURFACE OF HORIZONTAL PIPE MUST BE MAINTAINED FOR EVERY VENTING CONFIGURATION.
Figure 4.2, Mantel and Trim Requirements
16 FACING AND FINISHING
NON-COMBUSTIBLE ZONE
14" (356mm)
12" (305mm)
10" (254mm)
18"
¾
" (19 mm)
(457mm)
16"
(406mm)
10"
14"
(254mm)
(356mm)
½
" (13mm)
NON-COMBUSTIBLE
MATERIAL ONLY
FIREPLACE ENCLOSURE FLOOR
½
" (38mm) CLEARANCE TO COMBUSTIBLE MATERIAL ABOVE THE
UNLIMITED
SIDEWALL CLEARANCE
SINGLE VERTICAL
HEADER
54"
(1372mm)**
48"
(1219mm)*
1" (25mm)
1" (25mm)