Delta Controls
Product Specifications
Power Requirements
Power Consumption
Ambient Ratings
Communication Ports
Inputs
Technology
Listings
Compliance
Page 10 of 12
24 VAC, 60Hz, Class 2
8 VA
32° to 131°F (0° to 55°C), 10 to 90% RH (non condensing)
NET1
BACnet MS/TP (RS-485)
Communication: 9600, 19200, 38400, 76800 bps (Default)
Maximum of 99 controllers
NET2
LINKnet
Communication: 76800 bps
Maximum of 4 LINKnet controllers including up to two DFM
controllers
Service
RJ-11 Jack
Port
Used with Delta Controls service tool devices (for example,
CON-768)
16 Universal Inputs (10 bit), jumper configurable for the following input
types:
0-5 VDC
0-10 VDC
10 KΩ Thermistor
Dry Contact (using 10 KΩ Thermistor jumper setting)
4-20 mA
32 bit processor
1 MB (8 megabit) Flash Memory
127 KB SRAM memory
UL 916 Listed
BTL Listed
UL 864 Listed (DAC-1600-UL864 model only)
CE
FCC