14.2.1 If no password is set

action
1
Press OK
2
Set (ADV.SET) to Yes and press OK
3
Set SETUP to SIL and press OK
4
Set EN.SIL to YES and press OK
5
Set password to a number between 0 and
9999 and press OK
(At this time the device starts operating
in SIL mode with the entered configuration
parameters!)
6
Press OK to confirm verification of the OPEN-
>LOCK in the display
7
Verify input type and press OK
8
Verify fixed input current range and press OK
(ONLY if IN.TYPE = CURR)
9
Verify sensor connection type and press OK
(ONLY if IN.TYPE = TEMP and SENSOR = Ni or Pt
or IN.TYPE = LIN.R)
10
Verify temperature unit and press OK
(ONLY if IN.TYPE = TEMP)
11
Verify temperature sensor type and press OK
( ONLY if IN.TYPE = TEMP)
12
Verify Pt sensor type and press OK
(ONLY if IN.TYPE = TEMP and SENSOR = Pt)
13
Verify Ni sensor type and press OK
(ONLY if IN.TYPE = TEMP and SENSOR = Ni)
14
Verify Thermocouple type and press OK
(ONLY if IN.TYPE = TEMP and SENSOR = TC)
Note 7 : Open is shown briefly in the display.
Version No. V3R0
safety Manual
Display shows
ADV.SET
SETUP
EN.SIL
NEW.PAS
CONFIG
Verify
OPEN->LOCK
(Note 7 )
IN.TYPE
I.RANGE
CONNEC
UNIT
SENSOR
Pt.TYPE
Ni.TYPE
TC.TYPE
CJC