If No Password Is Set - PR 9100 Series Manual

Temperature/ma converter
Table of Contents

Advertisement

Safety Manual

14.2.1 If no password is set

1
2
3
4
5
6
7
8
9
10
11
12
13
14
14
9113 TeMperaTure / ma CONVerTer
action
Press OK
Set (ADV.SET) to Yes and press OK
Set SETUP to SIL and press OK
Set EN.SIL to YES and press OK
Set password to a number between 0 and
9999 and press OK
(At this time the device starts operating
in SIL mode with the entered configuration
parameters!)
Press OK to confirm verification of the OPEN-
>LOCK in the display
Verify input type for Channel 1 and press OK
Verify fixed input range and press OK
(ONLY IF CH1.TYP = CURR)
Verify sensor connection type and press OK
(ONLY IF SENSOR = Ni or Pt and CH1.TYP =
TEMP)
Verify temperature unit and press OK
(ONLY IF CH1.TYP = TEMP)
Verify temperature sensor type and press OK
( ONLY IF CH1.TYP = TEMP)
Verify Pt sensor type and press OK
(ONLY IF SENSOR = Pt and CH1.TYP = TEMP)
Verify Ni sensor type and press OK
(ONLY IF SENSOR = Ni and CH1.TYP = TEMP)
Verify Thermocouple type and press OK
(ONLY IF SENSOR = TC and CH1.TYP = TEMP)
* Open is shown briefly in the display.
Version No. V6R0
Display shows
ADV.SET
SETUP
EN.SIL
NEW.PAS
CONFIG
Verify
OPEN->LOCK*
CH1.TYP
I.RANGE
CONNEC
UNIT
SENSOR
Pt.TYPE
Ni.TYPE
TC.TYPE
CJC