Code
201
202
203
204
205
206
207
Designation
Description
Excessive mains volta-
As soon as the mains volta-
ge
ge, after detailed check, has
returned to the admissible
range, your FRONIUS IG
resumes feeding power into
the mains network
Insufficient mains
As soon as the mains volta-
voltage
ge, after a detailed check,
has returned to the admissi-
ble range, your FRONIUS
IG resumes feeding power
into the mains network
Excessive mains
As soon as the mains fre-
frequency
quency, after a detailed
check, has returned to the
admissible range, your
FRONIUS IG resumes fee-
ding power into the mains
network
Insufficient mains fre-
As soon as the mains fre-
quency
quency, after a detailed
check, has returned to the
admissible range, your
FRONIUS IG resumes fee-
ding power into the mains
network
Imbalance of mains
As soon as the mains impe-
network impedance
dance after a detailed check,
has returned to the admissi-
ble range, your FRONIUS
IG resumes feeding power
into the mains network
Absolute reading of
As soon as the mains impe-
mains impedance too
dance after detailed che-
high
cking, has returned to the
admissible range, your
FRONIUS IG resumes fee-
ding power into the mains
network
Problems with the
ENS recognises a faulty
mains relay
mains relay
67
Repair
Check mains voltage
If the service code does
not
disappear,
you
should contact your
installation specialist
Check mains voltage
If the service code does
not
disappear,
you
should contact your
installation specialist
Check mains frequency
If the service code does
not
disappear,
you
should contact your
installation specialist
Check mains frequency
If the service code does
not
disappear,
you
should contact your
installation specialist
Imbalance reaction can
be only short termed
Check in-house line ca-
ble cross section
Check ENS-Jumper
If Service-Code is dis-
played permanently, you
should contact a Fronius
trained service technici-
an