Rrtd Inputs - GE T60 Instruction Manual

Transformer protection system ur series
Hide thumbs Also See for T60:
Table of Contents

Advertisement

5.9 TRANSDUCER INPUTS AND OUTPUTS
Table 5–35: RTD TEMPERATURE VS. RESISTANCE
TEMPERATURE
°C
°F
–50
–58
–40
–40
–30
–22
–20
–4
–10
14
0
32
10
50
20
68
30
86
40
104
50
122
60
140
70
158
80
176
90
194
100
212
110
230
5
120
248
130
266
140
284
150
302
160
320
170
338
180
356
190
374
200
392
210
410
220
428
230
446
240
464
250
482
a) MAIN MENU

PATH: SETTINGS
TRANSDUCER I/O
 RRTD INPUTS
Menus are available to configure each of the remote RTDs.
5-316
RESISTANCE (IN OHMS)
100 Ω PT
120 Ω NI
(DIN 43760)
80.31
86.17
84.27
92.76
88.22
99.41
92.16
106.15
96.09
113.00
100.00
120.00
103.90
127.17
107.79
134.52
111.67
142.06
115.54
149.79
119.39
157.74
123.24
165.90
127.07
174.25
130.89
182.84
134.70
191.64
138.50
200.64
142.29
209.85
146.06
219.29
149.82
228.96
153.58
238.85
157.32
248.95
161.04
259.30
164.76
269.91
168.47
280.77
172.46
291.96
175.84
303.46
179.51
315.31
183.17
327.54
186.82
340.14
190.45
353.14
194.08
366.53


RRTD INPUTS

 RRTD
 RRTD
MESSAGE
 RRTD 12
MESSAGE
T60 Transformer Protection System
100 Ω NI
10 Ω CU
71.81
7.10
77.30
7.49
82.84
7.88
88.45
8.26
94.17
8.65
100.00
9.04
105.97
9.42
112.10
9.81
118.38
10.19
124.82
10.58
131.45
10.97
138.25
11.35
145.20
11.74
152.37
12.12
159.70
12.51
167.20
12.90
174.87
13.28
182.75
13.67
190.80
14.06
199.04
14.44
207.45
14.83
216.08
15.22
224.92
15.61
233.97
16.00
243.30
16.39
252.88
16.78
262.76
17.17
272.94
17.56
283.45
17.95
294.28
18.34
305.44
18.73
1
See page 5-317.
2
See page 5-317.
See page 5-317.
5 SETTINGS
5.9.3 RRTD INPUTS
GE Multilin

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents