Display Properties - GE T60 Instruction Manual

Transformer protection system ur series
Hide thumbs Also See for T60:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
Activity Value — 16 bit unsigned
ENUMERATION
DESCRIPTION
1
Authentication Failed
2
User Lockout
3
FW Upgrade
4
FW Lock
5
Settings Lock
6
Settings Change. Because this can fill the entire event log, it is supported by the
already existing Settings_Change.log file. This event is not required.
7
Clear Oscillography command
8
Clear Data Logger command (not applicable to all UR products)
9
Clear Demand Records command (not applicable to all UR products)
10
Clear Energy command (not applicable to all UR products)
11
Clear Unauthorized Access command
12
Clear Teleprotection Counters command (not applicable to all UR products)
13
Clear All Relay Records command
14
Role Log in
15
Role Log off
PATH: SETTINGS
PRODUCT SETUP
5
 DISPLAY
 PROPERTIES
Some relay messaging characteristics can be modified to suit different situations using the display properties settings.
LANGUAGE: This setting selects the language used to display settings, actual values, and targets. The setting dis-
plays when a language other than English was purchased, and the range depends on the order code of the relay.
FLASH MESSAGE TIME: Flash messages are status, warning, error, or information messages displayed for several
seconds in response to certain key presses during setting programming. These messages override any normal mes-
sages. The duration of a flash message on the display can be changed to accommodate different reading rates.
DEFAULT MESSAGE TIMEOUT: If the keypad is inactive for a period of time, the relay automatically reverts to a
default message. The inactivity time is modified via this setting to ensure messages remain on the screen long enough
during programming or reading of actual values.
5-24


DISPLAY PROPERTIES

LANGUAGE:
English
FLASH MESSAGE
MESSAGE
TIME:
1.0 s
DEFAULT MESSAGE
MESSAGE
TIMEOUT: 300 s
DEFAULT MESSAGE
MESSAGE
INTENSITY: 25 %
SCREEN SAVER
MESSAGE
FEATURE: Disabled
SCREEN SAVER WAIT
MESSAGE
TIME: 30 min
CURRENT CUT-OFF
MESSAGE
LEVEL: 0.020 pu
VOLTAGE CUT-OFF
MESSAGE
LEVEL: 1.0 V
T60 Transformer Protection System
5.2.2 DISPLAY PROPERTIES
Range: English; English, French; English, Russian;
English, Chinese
(range dependent on order code)
Range: 0.5 to 10.0 s in steps of 0.1
Range: 10 to 900 s in steps of 1
Range: 25%, 50%, 75%, 100%
Visible when a VFD is installed
Range: Disabled, Enabled
Visible when an LCD is installed
Range: 1 to 65535 min. in steps of 1
Visible when an LCD is installed
Range: 0.002 to 0.020 pu in steps of 0.001
Range: 0.1 to 1.0 V secondary in steps of 0.1
5 SETTINGS
GE Multilin

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents