Oscillography records contain waveforms captured at the sampling rate as well as other relay data at the point of trigger.
Oscillography records are triggered by a programmable FlexLogic operand. Multiple oscillography records may be captured
simultaneously.
The
is selectable, but the number of cycles captured in a single record varies considerably based on
NUMBER OF RECORDS
other factors such as sample rate and the number of operational modules. There is a fixed amount of data storage for oscil-
lography; the more data captured, the less the number of cycles captured per record. See the

RECORDS

OSCILLOGRAPHY

ple configurations with corresponding cycles/record. The minimum number of oscillographic records is three.
Table 5–6: OSCILLOGRAPHY CYCLES/RECORD EXAMPLE
RECORDS
CT/VTS
3
1
3
1
8
1
8
1
8
2
8
2
8
2
8
2
32
2
A new record may automatically overwrite an older record if
Set the
to a percentage of the total buffer size (for example, 10%, 50%, 75%, etc.). A trigger position of
TRIGGER POSITION
25% consists of 25% pre- and 75% post-trigger data. The
any FlexLogic parameter (element state, contact input, virtual output, etc.). The relay sampling rate is 64 samples per cycle.
The
setting determines the sampling rate at which AC input signals (that is, current and voltage) are
AC INPUT WAVEFORMS
stored. Reducing the sampling rate allows longer records to be stored. This setting has no effect on the internal sampling
rate of the relay which is always 64 samples per cycle; that is, it has no effect on the fundamental calculations of the device.
When changes are made to the oscillography settings, all existing oscillography records will be CLEARED.
NOTE
GE Multilin

OSCILLOGRAPHY
NUMBER OF RECORDS:
5
TRIGGER MODE:
Automatic Overwrite
TRIGGER POSITION:
50%
TRIGGER SOURCE:
Off
AC INPUT WAVEFORMS:
16 samples/cycle
 DIGITAL CHANNELS
 ANALOG CHANNELS
menu to view the number of cycles captured per record. The following table provides sam-
SAMPLE
DIGITALS
RATE
8
0
16
16
16
16
16
16
16
16
16
63
32
63
64
63
64
63
TRIGGER MODE
TRIGGER SOURCE
T60 Transformer Protection System
Range: 1 to 64 in steps of 1
Range: Automatic Overwrite, Protected
Range: 0 to 100% in steps of 1
Range: FlexLogic operand
Range: Off; 8, 16, 32, 64 samples/cycle
ANALOGS
CYCLES/
RECORD
0
14663
0
6945
0
3472
4
2868
4
1691
16
1221
16
749
16
422
16
124
is set to "Automatic Overwrite".
is always captured in oscillography and may be
5.2 PRODUCT SETUP
5.2.8 OSCILLOGRAPHY
5

ACTUAL VALUES
5-65