4 HUMAN INTERFACES
There are several places where text messages can be programmed to allow the relay to be customized for specific applica-
tions. One example is the Message Scratchpad. Use the following procedure to enter alphanumeric text messages.
For example: to enter the text, "Breaker #1".
1.
Press the decimal point to enter text edit mode.
2.
Press the VALUE keys until the character 'B' appears; press the decimal key to advance the cursor to the next position.
3.
Repeat step 2 for the remaining characters: r,e,a,k,e,r, ,#,1.
4.
Press ENTER to store the text.
5.
If you have any problem, press HELP to view context sensitive help. Flash messages appear sequentially for several
seconds each. For the case of a text setting message, pressing HELP displays how to edit and store new values.
d) ACTIVATING THE RELAY
RELAY SETTINGS:
Not Programmed
To change the
RELAY SETTINGS
1.
Press the MENU key until the
display.
2.
Press the MESSAGE RIGHT key until the
3.
Press the MESSAGE DOWN key until the
4.
Press the MESSAGE RIGHT key until the

SETTINGS

 SETTINGS
 PRODUCT SETUP
5.
After the
RELAY SETTINGS:
selection to "Programmed".
6.
Press the ENTER key.
RELAY SETTINGS:
Not Programmed
7.
When the "NEW SETTING HAS BEEN STORED" message appears, the relay is in "Programmed" state and the In
Service LED turns on.
e) ENTERING INITIAL PASSWORDS
The information in this section refers to password security. For information on how to set or change CyberSentry pass-
words, see the Settings > Product Setup > Security > CyberSentry section in the next chapter.
GE Multilin
When the relay is powered up, the Trouble LED is on, the In Service LED off, and this
message displayed, indicating the relay is in the "Not Programmed" state and is safe-
guarding (output relays blocked) against the installation of a relay whose settings have
not been entered. This message remains until the relay is explicitly put in the "Pro-
grammed" state.
: "Not Programmed" mode to "Programmed", proceed as follows:
header flashes momentarily and the
SETTINGS
message appears on the display.
SECURITY
INSTALLATION
RELAY SETTINGS:
 SECURITY
 DISPLAY
 PROPERTIES
 INSTALLATION
Not Programmed message appears on the display, press the VALUE keys change the
RELAY SETTINGS:
Programmed
T60 Transformer Protection System
4.3 FACEPLATE INTERFACE
PRODUCT SETUP
message appears on the display.
Not Programmed message is displayed.
NEW SETTING
HAS BEEN STORED
message appears on the
RELAY SETTINGS:
Not Programmed
4-27