5 SETTINGS
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
 COMMUNICATIONS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
b) SERIAL PORTS
The T60 is equipped with up to two independent serial communication ports. The faceplate RS232 port is intended for local
use and is fixed at 19200 baud and no parity. The rear COM2 port be used for either RS485 or RRTD communications.
PATH: SETTINGS
PRODUCT SETUP
 SERIAL PORTS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
It is important that the baud rate and parity settings agree with the settings used on the computer or other equipment that is
connected to these ports.
GE Multilin


COMMUNICATIONS

 SERIAL PORTS
 NETWORK
 ROUTING
 MODBUS PROTOCOL
 DNP PROTOCOL
 DNP / IEC104
 POINT LISTS
 IEC 61850 PROTOCOL
 WEB SERVER
 HTTP PROTOCOL
 TFTP PROTOCOL
 IEC 60870-5-104
 PROTOCOL
 EGD PROTOCOL

COMMUNICATIONS
SERIAL PORTS
COM2 USAGE:
RS485
RRTD SLAVE ADDRESS:
254
RS485 COM2 BAUD
RATE: 19200
RRTD BAUD RATE:
19200
RS485 COM2 PARITY:
None
RS485 COM2 RESPONSE
MIN TIME:
0 ms
T60 Transformer Protection System
5.2 PRODUCT SETUP
5.2.4 COMMUNICATIONS
See below.
See page 5–30.
See page 5–33.
See page 5–35.
See page 5–36.
See page 5–39.
See page 5–40.
See page 5–55.
See page 5–55.
See page 5–56.
See page 5–57.
Range: RS485, RRTD
Range: 1 to 254 in steps of 1. Shown only if the COM2
USAGE setting is "RRTD".
Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, 115200. Shown
only if the COM2 USAGE is setting is "RS485".
Range: 1200, 2400, 4800, 9600, 19200. Shown only if
the COM2 USAGE is setting is "RRTD".
Range: None, Odd, Even.
Range: 0 to 1000 ms in steps of 10.