GE T60 Instruction Manual page 630

Transformer protection system ur series
Hide thumbs Also See for T60:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 62 of 69)
ADDR
REGISTER NAME
Remote Devices (Read/Write Setting) (16 modules)
CB00
Remote Device 1 GSSE/GOOSE Application ID (GOID)
CB21
Remote Device 1 GOOSE Ethernet APPID
CB22
Remote Device 1 GOOSE Dataset
B
CB23
Remote Device 1 in PMU Scheme
CB24
Reserved
CB25
...Repeated for Device 2
CB4A
...Repeated for Device 3
CB6F
...Repeated for Device 4
CB94
...Repeated for Device 5
CBB9
...Repeated for Device 6
CBDE
...Repeated for Device 7
CC03
...Repeated for Device 8
CC28
...Repeated for Device 9
CC4D
...Repeated for Device 10
CC72
...Repeated for Device 11
CC97
...Repeated for Device 12
CCBC
...Repeated for Device 13
CCE1
...Repeated for Device 14
CD06
...Repeated for Device 15
CD2B
...Repeated for Device 16
Remote Inputs (Read/Write Setting) (32 modules)
CFA0
Remote Input 1 Device
CFA1
Remote Input 1 Bit Pair
CFA2
Remote Input 1 Default State
CFA3
Remote Input 1 Events
CFA4
Remote Input 1 Name
CFAA
...Repeated for Remote Input 2
CFB4
...Repeated for Remote Input 3
CFBE
...Repeated for Remote Input 4
CFC8
...Repeated for Remote Input 5
CFD2
...Repeated for Remote Input 6
CFDC
...Repeated for Remote Input 7
CFE6
...Repeated for Remote Input 8
CFF0
...Repeated for Remote Input 9
CFFA
...Repeated for Remote Input 10
D004
...Repeated for Remote Input 11
D00E
...Repeated for Remote Input 12
D018
...Repeated for Remote Input 13
D022
...Repeated for Remote Input 14
D02C
...Repeated for Remote Input 15
D036
...Repeated for Remote Input 16
D040
...Repeated for Remote Input 17
D04A
...Repeated for Remote Input 18
D054
...Repeated for Remote Input 19
D05E
...Repeated for Remote Input 20
D068
...Repeated for Remote Input 21
D072
...Repeated for Remote Input 22
D07C
...Repeated for Remote Input 23
D086
...Repeated for Remote Input 24
D090
...Repeated for Remote Input 25
D09A
...Repeated for Remote Input 26
D0A4
...Repeated for Remote Input 27
B-70
RANGE
---
0 to 16383
0 to 16
0 to 1
0 to 3
1 to 32
0 to 96
0 to 3
0 to 1
1 to 64
T60 Transformer Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
---
F209
"Remote Device
---
1
F001
---
1
F184
---
1
F126
---
1
F626
---
1
F001
---
1
F156
---
1
F086
---
1
F102
---
1
F205
DEFAULT
1"
0
0 (Fixed)
0 (No)
0 (None)
1
0 (None)
0 (Off)
0 (Disabled)
"Rem Ip 1"
GE Multilin

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents