GE T60 Instruction Manual page 612

Transformer protection system ur series
Hide thumbs Also See for T60:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 44 of 69)
ADDR
REGISTER NAME
9267
RRTD RTD 1 Type
9268
RRTD RTD 1 Application
9269
RRTD RTD 1 Alarm Temp
926A
RRTD RTD 1 Alarm Pickup Delay
B
926B
RRTD RTD 1 Trip Temp
926C
RRTD RTD 1 Trip Pickup Delay
926D
RRTD RTD 1 Trip Reset Delay
926E
RRTD RTD 1 Trip Voting
926F
RRTD RTD 1 Block
9271
RRTD RTD 1 Open
9272
RRTD RTD 1 Target
9273
RRTD RTD 1 Events
9274
...Repeated for module number 2
9288
...Repeated for module number 3
929C
...Repeated for module number 4
92B0
...Repeated for module number 5
92C4
...Repeated for module number 6
92D8
...Repeated for module number 7
92EC
...Repeated for module number 8
9300
...Repeated for module number 9
9314
...Repeated for module number 10
9328
...Repeated for module number 11
933C
...Repeated for module number 12
DCmA Outputs (Read/Write Setting) (24 modules)
9360
DCmA Output 1 Source
9361
DCmA Output 1 Range
9362
DCmA Output 1 Minimum
9364
DCmA Output 1 Maximum
9366
...Repeated for DCmA Output 2
936C
...Repeated for DCmA Output 3
9372
...Repeated for DCmA Output 4
9378
...Repeated for DCmA Output 5
937E
...Repeated for DCmA Output 6
9384
...Repeated for DCmA Output 7
938A
...Repeated for DCmA Output 8
9390
...Repeated for DCmA Output 9
9396
...Repeated for DCmA Output 10
939C
...Repeated for DCmA Output 11
93A2
...Repeated for DCmA Output 12
93A8
...Repeated for DCmA Output 13
93AE
...Repeated for DCmA Output 14
93B4
...Repeated for DCmA Output 15
93BA
...Repeated for DCmA Output 16
93C0
...Repeated for DCmA Output 17
93C6
...Repeated for DCmA Output 18
93CC
...Repeated for DCmA Output 19
93D2
...Repeated for DCmA Output 20
93D8
...Repeated for DCmA Output 21
93DE
...Repeated for DCmA Output 22
93E4
...Repeated for DCmA Output 23
93EA
...Repeated for DCmA Output 24
Direct Input/Output Names (Read/Write Setting) (32 modules)
9400
Direct Input 1 Name
B-52
RANGE
0 to 3
0 to 5
1 to 200
5 to 600
1 to 200
5 to 600
5 to 600
0 to 13
0 to 4294967295
0 to 2
0 to 2
0 to 1
0 to 65535
0 to 2
–90 to 90
–90 to 90
0 to 96
T60 Transformer Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F174
---
1
F550
°C
1
F001
s
5
F001
°C
1
F001
s
5
F001
s
5
F001
---
1
F603
---
1
F300
---
1
F552
---
1
F109
---
1
F102
---
1
F600
---
1
F522
0 (–1 to 1 mA)
pu
0.001
F004
pu
0.001
F004
---
1
F205
DEFAULT
0 (100 Ohm
Platinum)
0 (None)
130
5
130
5
5
0 (None)
0
0 (None)
0 (Self-reset)
0 (Disabled)
0
0
1000
"Dir Ip 1"
GE Multilin

Hide quick links: