Setting via control panel
1. Mark the Settings menu with
2. Mark Primary controller with
3. Mark Primary sensor with
4. Mark Go to setting of analog input with
press
.
Now the display Analog inputs (4.3.8) appears. Select the
analog input (AI) for the primary sensor, and set the
parameters for this sensor. Return to display Primary sensor
(4.1.4) with
.
5. Select the control parameter for the primary sensor with
or
, and press
.
Factory setting
The primary parameter is discharge pressure. The sensor is
connected to AI1 (CU 351). Other primary parameters can be
selected in the start-up wizard.
11.7.8 Clock program (4.1.6)
Fig. 40 Clock program
Description
With this function, it is possible to set setpoints and day and time
for their activation. It is also possible to set day and time for stop
of the system.
If the clock program is deactivated, the setpoint of the program
will remain active.
Minimum 2 events are required when activating
the clock program; one to start the system and
Note
one to stop the system.
30
.
or
, and press
.
or
, and press
.
or
, and
Setting range
•
Activation of the function.
•
Activation and setting of event.
Setting via control panel
1. Mark the Settings menu with
2. Mark Primary controller with
3. Mark Clock program with
4. Mark Event 1 with
or
Fig. 41 Event 1
5. Mark operating mode Normal or Stop with
press
. (If Stop is selected, step 6 will be skipped.)
6. Mark Setpoint, closed loop with
Set the pressure with
7. Mark Time (hours, minutes) with
8. Set the time with
or
9. Mark day of week on which the settings are to be activated
with
or
, and press
10. Mark Activated with
11. Repeat steps 4 to 10 if several events are to be activated.
Note: Up to ten events can be set.
12. Return with
.
13. Mark Activated with
mark in the right box shows that the function has been
activated.
Factory setting
The function is deactivated.
.
or
, and press
or
, and press
, and press
.
or
or
.
or
, and save with
.
or
.
, and save with
.
.
or
, and press
.
or
, and press
. The check
.
.
, and