Procedures For Checking The Accessories - ABB SACE Emax 2 Installation, Operation And Maintenance Instructions

Low voltage air circuit-breakers
Table of Contents

Advertisement

Procedures for checking the
accessories
90 | © 2014 ABB | 1SDH000999R0002 - L8569
The following procedures for checking the accessories are to be performed before they are put into service:
Accessories
(*)
to
Procedure
be checked
1. Power the gearmotor for loading the springs at the relevant rated voltage.
Result: The springs are loaded correctly. The signals are normal. When the
springs are loaded the gearmotor stops.
Gearmotor
2. Perform some closing and opening operations.
Result: The gearmotor reloads the springs after every closing operation.
1. Power the under-voltage coil at the relevant rated voltage and perform the clos-
ing operation on the circuit-breaker.
Result: The circuit-breaker closes correctly; the signallings are normal.
2. Turn off the voltage supply to the release. The circuit-breaker opens.
3. Power the under-voltage coil at the relevant rated voltage and perform the clos-
ing operation on the circuit-breaker.
Under-voltage coil
Result: The circuit-breaker closes; the signal changes over.
failure, the circuit-breaker can be closed only after the coil has been
energized electrically. Make sure that the coil has effectively been
tripped by a power failure. Otherwise, examine the circuit-breaker and
associated device to make sure that they are in a good condition.
1. Close the circuit-breaker.
2. Power the opening coil at the relevant rated voltage.
Opening coil
Result: The circuit-breaker opens correctly; the signals are normal.
1. Open the circuit-breaker.
2. Load the springs manually or electrically.
Closing coil
3. Power the closing coil at its rated voltage.
Result: The circuit-breaker closes correctly; the signals are normal.
1. Power the protection release with the Vaux auxiliary power supply.
2. Power the Ekip Com Actuator contacts.
3. Close the circuit-breaker
4. Select "open CB" from the Ekip Touch menu
Opening coil with Ekip
Com Actuator
Result: The circuit-breaker opens correctly; the signals are normal.
energized.
(*)
if present.
(**) only withdrawable versions.
NOTE! If present, power the under-voltage coil in advance.
WARNING! If the under-voltage coil has been tripped by a power
NOTE! The test can be performed if the release and the coils are
Putting into service and maintenance | 1 - Putting into service
ABB | SACE Emax 2
Continued on the next page