Protection G

t
I4
t4
40 | © 2014 ABB | 1SDH000999R0002 - L8569
The protection G protects against an earth fault.
NOTE: the protection is available for the LSIG version of the release.
G
When the activation threshold is exceeded, the protection trips within a fixed or dynamic time (the time
decreases as the current read increases).
Parameters
All the parameters that can be modified by the user affect the response curve, and related tripping times.
I
Parameter
Enable
Type of curve
Threshold I4
Time t3
Description
By setting the dip-switches of the threshold in one of the available combinations
other than Off, the protection is enabled.
If enabled, the protection is inhibited automatically by the release in two conditions:
• Disconnection of one or more current sensors.
• Current measured on one of the phases is higher than a maximum value.
IMPORTANT: the maximum current value that deactivates protection G
varies according to the threshold set:
• 8 In (with I4 ≥ 0.8 In)
• 6 In (with 0.5 In ≤ I4 < 0.8 In)
• 4 In (with 0.2 In ≤ I4 < 0.5 In)
• 2 In (with I4 < 0.2 In)
Determines the dynamic of the curve and the tripping time, fixed or dynamic accord-
ing to the selection:
NOTE: calculation of the tripping time of the inverse time curve is based on a
mathematical expression. The details are provided in the table on page 43.
It defines the current value that if exceeded activates the protection (in reference to
the curve, it is the part parallel to the ordinate).
IMPORTANT:
• The delay is interrupted if the current drops below the tripping
threshold.
• For all the UL versions the maximum threshold allowed by the re-
lease is 1200 A. If a higher value is set, the release signals the error and
forces the parameter to 1200 A.
The selected function determines the contribution of t4:
• Fixed time: t4 is the delay time between the exceeding of the I4 threshold and the
sending of the opening command.
• Dynamic time: t4 contributes in calculating the tripping time (in reference to the
curve, t4 affects the entire curve, shifting it as a whole along the vertical axis).
IMPORTANT:
• The minimum tripping time of the protection is t4. If, according to
the calculation, the tripping time is less, it is automatically limited to t4.
• For all the UL versions, the maximum time allowed by the release is
0.4s. If a higher value is set, the release signals the error and forces the
parameter to 0.4 s.
ABB | SACE Emax 2
Ekip Dip protection release | 2 - Protections