Some led signals indicate connection errors or operational errors that require corrective or maintenance
operations. The following are the suggestions for checking referring to the preceding LED table:
HELP note
Operation
A
Contact ABB.
Check the connections between release and accessories (Rating Plug, trip coil, sen-
B
sors, etc).
C
Normal operation/signalling provided by the release.
Error in setting of the dip-switches. Check and correct the following conditions:
• All the dip-switches of L are in the ON position
• I1 > I2 or I2 > I3.
• Iu < (2 * In * I1) in the case where InN = 200 %.
D
• I4 < the highest between 100 A and 0.3 In, in the absence of auxiliary power
supply.
• t2 > 0,4s (in the case of circuit breaker UL)
• t4 > 0,4s (in the case of circuit breaker UL)
• I4 > 1200 A (in the case of UL circuit-breaker)
E
Carry out installation.
F
Connect via Ekip Connect in order to set the Local Bus or to confirm maintenance.
G
Contact ABB to restore software compatibility between Ekip Dip and Mainboard.
H
Replace the battery.
Ekip Dip protection release | 5 - List of alarms and signals
ABB | SACE Emax 2