M: Motor - ABB SACE Emax 2 Installation, Operation And Maintenance Instructions

Low voltage air circuit-breakers
Table of Contents

Advertisement

M: motor

U1
U2
M
76 | © 2014 ABB | 1SDH000999R0002 - L8569
The motor automatically recharges the closing springs of the circuit-breaker when these are discharged.
The motor is equipped with a limit contact S33 M/1 that interrupts the power supply of the motor after loading
of the springs is completed.
The motor is equipped with a limit contact S33 M/2 that signals the state of the loaded springs.For information
on the S33 M/2 limit contact refer to the dedicated paragraph "S33 M/2: springs loaded signalling contact"
in this chapter.
NOTE: The closing springs can in any case be loaded manually through the appropriate front
control lever.
The tables listing the available voltages and the electrical characteristics are provided below:
Available voltages (Un)
24V...30V AC/DC
48V...60V AC/DC
100V...130V AC/DC
220V...250V AC/DC
380V...415V AC
M: Connections
Further information is available on page 58, or on the site http://www.abb.com/abblibrary/DownloadCenter/,
where the wiring diagram is available 1SDM000091R0001.
Diagram 13
Information on the assembly is available from the web site http://www.abb.com/abblibrary/DownloadCenter/,
in particular with the kit sheet 1SDH000999R0609.
General characteristics
Operating limits
Inrush power (Ps)
Continuous power (Pc)
Charging time
13
+
A4
~
X
U1
XV
U1
XB1
1
S33M/1
A1
F1
M
XB1
2
XV
U2
X
U2
-
A4
~
Electrical accessories | 1 - Electrical control accessories
ABB | SACE Emax 2
85...110 %Un
500 VA/W
100 VA/W
Min 5 s, max 10 s