Faults Signalled On The Display - ABB SACE Emax 2 Installation, Operation And Maintenance Instructions

Low voltage air circuit-breakers
Table of Contents

Advertisement

Faults signalled on the display The following is a list of faults that can be detected from the display and the suggestions for resolving them:
97 | © 2014 ABB | 1SDH000999R0002 - L8569
Signal
No Com on Local Bus
warning
Trip coil disconnected
Contact Wear PreAlarm/
Alarm
L1/L2/L3/Ne sensor
disconnected
Gext sensor Disconnected
Rating Plug Error
Internal Error
Invalid Date
CB Status Error
Rating Plug Installation
Warning
Switchboard Actors Com-
munication Error
Battery Low
Voltage module Installation
warning
Voltage Module Error
Software Not Compatible
(1)
Further information is available from the web site http://www.abb.com/abblibrary/DownloadCenter/, where
the procedure is available 1SDH001000R0509.
Consult the individual chapters describing the modules for fault finding and resolving with regard to Ekip Com
modules.
Suggestions
Local bus enabled bus but no module present: check connection to termi-
nal box modules (example: Ekip Supply, Com, Contact, ecc...)
Check the connection of the opening solenoid
Make sure that the contacts/poles are in good condition.
Check the connection of the current sensor
Check the connection of the current sensor
Check the Rating Plug connection on the front of the protection release.
Contact ABB
Set the date
Check the circuit-breaker status signal contacts
Install Rating Plug, and in the case of faults check its connection
Check the configuration and connection of the Ekip Link modules
Change the battery on the release
Install the module
Error reading the module parameters. Contact ABB
Software versions between Mainboard and Ekip Touch are not compatible
with each other: editing of all parameters is inhibited on the display.
Protections L, I and Iinst are activated and operative with the parameters
entered in the previous protection release.
Please consult ABB if compatibility needs to be restored.
Putting into service and maintenance | 2 - Identification of alarms or failures
ABB | SACE Emax 2