4 - Other accessories

Rating Plug The Rating Plug defines the rated current In, necessary in order to set the current protections on the release,
Ekip Connect software Ekip Connect is the free software for communication and testing of ABB low voltage circuit-breakers equipped
67 | © 2014 ABB | 1SDH000999R0002 - L8569
where these refer to In.
It is supplied with all Ekip releases, mounted on a front connector dedicated and accessible to the user, and
can be replaced with release off and circuit breaker open.
IMPORTANT: the replacement of the Rating Plug with release on or circuit breaker
closed may cause malfunction of the release, or unwanted opening of the switch.
NOTE: a trip unit can be equipped with any Rating Plug with a rated current of up to Iu, i.e.
the rated uninterrupted current of the circuit-breaker (indicate on the rating plate of the circuit-
breaker).
The release continuously checks for the presence of the Rating Plug, signalling its absence or any errors in
assembly or installation.
Once mounted, when the release is energized, its installation is requested.
On the Touch, Hi-Touch, G Touch and G Hi-Touch releases to activate the residual current protection, it is
necessary to mount a Rating Plug Rc. They are also available Rating Plug L = OFF, which allow you to cancel
the protection L.
Further information on mounting the Rating Plug is available from the web site http://www.abb.com/
abblibrary/DownloadCenter/, in particular in the kit sheet 1SDH001000R0510.
with compatible releases, in particular Ekip releases.
It must be installed on PCs equipped with the Microsoft Windows® operating system by downloading it from
the site http://www.abb.com/abblibrary/DownloadCenter.
With its communication function, it allows you to:
• Monitor the state of the circuit-breakers connected and record information.
• Execute the operation, reset, signalling commands, etc...
• Configure the protection releases with customized parameters.
• Configure the electronic accessories, connected to the release via Local Bus.
• Download information from releases equipped with Datalogger.
• Create communication reports.
• Reset configurations.
With test function, and Ekip T&P module (see page 68), it allows you to:
• Simulate fault conditions by performing manual or automatic tests.
• Perform trip tests.
• Create test reports.
Further information on the Ekip Connect application is available from the web site http://www.abb.com/
abblibrary/DownloadCenter/, in particular in the manual 1SDH000891R0002.