Figure 132: Vts Logic (P643 And P645 With 3-Phase Vts) - GE P642 Technical Manual

Micom p40 agile transformer protection ied
Table of Contents

Advertisement

P64x
All Poles Dead
IA
VTS I> Inhibit
IB
VTS I> Inhibit
IC
VTS I> Inhibit
VAB
Hardcoded threshold
VBC
Hardcoded threshold
Delta IA
Hardcoded threshold
Delta IB
Hardcoded threshold
Delta IC
Hardcoded threshold
V2
Hardcoded threshold
I2
I2>1 Current Set
VTS Reset Mode
Manual
Auto
MCB/VTS
VTS Status
Indication
Blocking
Any Pole Dead
VTS Acc Ind
V01225

Figure 132: VTS logic (P643 and P645 with 3-phase VTs)

For the P643 and P645, a 3-phase VT is used and each of the input voltages VA, VB and VC are with respect to
earth. For the P642, two single-phase VTs are used and the two input voltages VA and VB are phase-to-phase
voltages
As can be seen from the diagram, the VTS function is inhibited if:
An All Poles Dead DDB signal is present
A phase overcurrent condition exists
A Negative Phase Sequence current exists
If the phase current changes over the period of 1 cycle
The VTS will operate if:
All three of the input voltages are lower than the VTS Pickup threshold AND the function is not inhibited by
any of the above criteria
Negative Sequence Voltage is present AND the function is not inhibited by any of the above criteria
P64x-TM-EN-1.3
1
&
1
1
&
S
Q
R
&
&
&
1
&
Note: This diagram does not show all stages . Other stages follow similar principles.
S
&
Q
R
1
S
&
R
Chapter 14 - Supervision
1
&
VTS Slow Block
1
&
VTS Fast Block
1
VT Fail Alarm
Q
289

Advertisement

Table of Contents
loading

This manual is also suitable for:

P643P645

Table of Contents