Chapter 21 - Technical Specifications
16

ELECTROMAGNETIC COMPATIBILITY

16.1

1 MHZ BURST HIGH FREQUENCY DISTURBANCE TEST

Compliance
Common-mode test voltage (level 3)
Differential test voltage (level 3)
16.2

DAMPED OSCILLATORY TEST

Compliance
Common-mode test voltage (level 3)
Common-mode test voltage (level 4)
Differential mode test voltage
16.3

IMMUNITY TO ELECTROSTATIC DISCHARGE

Compliance
Class 4 Condition
Class 3 Condition
16.4

ELECTRICAL FAST TRANSIENT OR BURST REQUIREMENTS

Compliance
Applied to communication inputs
Applied to power supply and all other inputs
except for communication inputs
16.5

SURGE WITHSTAND CAPABILITY

Compliance
Condition 1
Condition 2
480
IEC 60255-22-1: 2008, Class III, IEC 60255-26:2013
2.5 kV
1.0 kV
EN61000-4-18: 2011: Level 3, 100 kHz and 1 MHz. Level 4: 3 MHz,
10 MHz and 30 MHz, IEC 60255-26:2013
2.5 kV
4.0 kV
1.0 kV
IEC 60255-22-2: 2009 Class 3 and Class 4, IEC 60255-26:2013
15 kV discharge in air to user interface, display, and exposed metalwork
8 kV discharge in air to all communication ports
IEC 60255-22-4: 2008 and EN61000-4-4:2004. Test severity level lll and lV, IEC
60255-26:2013
Amplitude: 2 kV, burst frequency 5 kHz and 100 KHz (level 4)
Amplitude: 4 kV, burst frequency 5 kHz and 100 KHz (level 4)
IEEE/ANSI C37.90.1: 2002
4 kV fast transient and 2.5 kV oscillatory applied common mode and differential
mode to opto inputs, output relays, CTs, VTs, power supply
4 kV fast transient and 2.5 kV oscillatory applied common mode to communications,
IRIG-B
P64x
P64x-TM-EN-1.3