Test disturbance voltage
Test using AM
Spot tests
16.11

MAGNETIC FIELD IMMUNITY

Compliance
IEC 61000-4-8 test
IEC 61000-4-9 test
IEC 61000-4-10 test
16.12

CONDUCTED EMISSIONS

Compliance
Power supply test 1
Power supply test 2
RJ45 test 1 (where applicable)
RJ45 test 2 (where applicable)
16.13

RADIATED EMISSIONS

Compliance
Test 1
Test 2
Test 3
16.14

POWER FREQUENCY

Compliance
Opto-inputs (Compliance is achieved using the opto-input
filter)
Note:
Compliance is achieved using the opto-input filter.
482
10 V rms
1 kHz @ 80%
27 MHz and 68 MHz
IEC 61000-4-8: 2009 Level 5
IEC 61000-4-9/10: 2001 Level 5
100 A/m applied continuously, 1000 A/m applied for 3 s
1000 A/m applied in all planes
100 A/m applied in all planes at 100 kHz/1 MHz with a burst duration of 2
seconds
EN 55022: 2010, IEC 60255-26:2013
0.15 - 0.5 MHz, 79 dBµV (quasi peak) 66 dBµV (average)
0.5 – 30 MHz, 73 dBµV (quasi peak) 60 dBµV (average)
0.15 - 0.5 MHz, 97 dBµV (quasi peak) 84 dBµV (average)
0.5 – 30 MHz, 87 dBµV (quasi peak) 74 dBµV (average)
EN 55022: 2010, IEC 60255-26:2013
30 – 230 MHz, 40 dBµV/m at 10 m measurement distance
230 – 1 GHz, 47 dBµV/m at 10 m measurement distance
1 – 2 GHz, 76 dBµV/m at 10 m measurement distance
IEC 60255-22-7:2003, IEC 60255-26:2013
300 V common-mode (Class A)
150 V differential mode (Class A)