Example 1: Two-Winding Transformer - No Tap Changer; Figure 51: Triple Slope Characteristic; Figure 52: P642 Used To Protect A Two Winding Transformer - GE P642 Technical Manual

Micom p40 agile transformer protection ied
Table of Contents

Advertisement

Chapter 6 - Transformer Differential Protection
V03110

Figure 51: Triple slope characteristic

5.2

EXAMPLE 1: TWO-WINDING TRANSFORMER - NO TAP CHANGER

Consider a two-winding power transformer with the following specifications:
Power rating: 90 MVA Transformer
Connection type: YNd9
Voltage specification 132:33 kV.
HV CT ratio: 400:1
LV CT ratio: 2000:1
Percentage reactance: 10%
A
B
C
V03115

Figure 52: P642 used to protect a two winding transformer

122
Idiff/Inom
Is-HS2
Is-HS1
Operate region
Is1
90 MVA
132 kV/33 kV
YNd9
400:1
Protected zone
B
Phase & amplitude
Correction
+
Zero sequence filtering
D
Restraint region
K2
K1
TC and CT errors
Is2
Earthing
transformer
B
Phase & amplitude
Correction
B
B
Zero sequence filtering
B
B
D
D
Ibias /Inom
2000:1
a
b
c
+
P642
P64x-TM-EN-1.3
P64x