Establishing connection and verifying the IEC 61850 communication
Section 10
10.1
10.2
Generator protection REG670 2.0 IEC
Commissioning manual
Establishing connection and verifying the
IEC 61850 communication

Overview

The rear OEM ports are used for:
substation bus (IEC 61850-8-1) communication.
For IEC 61850-8-1 redundant communication, both rear OEM ports are utilized.

Setting the station communication

To enable IEC 61850 communication the corresponding OEM ports must be
activated. The rear OEM port AB and CD is used for IEC 61850-8-1 communication.
For IEC 61850-8-1 redundant communication, both OEM port AB and CD are used
exclusively.
To enable IEC 61850 station communication:
1.
Enable IEC 61850-8-1 (substation bus) communication for port AB.
1.1. Set values for the rear ports AB and CD.
Navigate to: Main menu/Configuration/Communication/Ethernet
configuration/LANAB:1
Set values for Mode, IPAddress and IPMask. Mode must be set to Normal.
Check that the correct IP address is assigned to the port.
1.2. Enable IEC 61850-8-1 communication.
Navigate to: Main menu/Configuration/Communication/Station
communication/IEC61850-8-1/IEC61850–8–1:1
Set Operation to On and PortSelGOOSE to the port used (for example
LANAB).
2.
Enable redundant IEC 61850-8-1 communication for port AB and CD
2.1. Enable redundant communication.
Navigate to: Main menu/Configuration/Communication/Ethernet
configuration/PRP:1
Set values for Operation, IPAddress and IPMask. Operation must be set to
On.