Acquiring References - ABB REG670 2.0 IEC Commissioning Manual

Relion 670 series generator protection
Table of Contents

Advertisement

1MRK502053-UEN B
7.5
Generator protection REG670 2.0 IEC
Commissioning manual
Calibrating injection based 100% stator earth fault protection
GUID-D024D8B7-45F3-42D1-AAA3-488A2996267B V1 EN
Figure 23:
ICT calibration tab 4
13. Before proceeding any further make sure that you have removed the short-circuit
that was applied during calibration step 3.
14. To finish the calibration process, select the Submit to Parameter setting
button.
15. In Parameter setting, write the newly acquired parameters to IED.

Acquiring references

To detect different operation conditions of the generator and select proper impedance
reference requires logic outside the injection function. Therefore changing/switching
impedance reference is not described here but in a separate application note
1MRG005030 Application example for injection based 100% Stator EF and Sensitive
Rotor EF protection.
The injection commissioning tool (ICT) helps the commissioning engineer to acquire
additional references for different conditions of the generator. The below description
assumes that reference 1 was set during calibration and that a second reference must
be set now.
Section 7
IEC11000048-2-en.vsd