Section 12
Testing functionality by secondary injection
116
Table 14:
Test points for phase-to-phase loops L1-L2 (Ohm/Loop)
Test point
Reach
Set value
1
X
X1
R
0
2
X
X1
R
R1
3
X
0.8 x X1
R
0.8 x R1
4
X
0.5 x X1
R
0.5 x R1
5
X
0.85 x RFPP x tan (ArgLd)
R
0.85 x RFPP
6
X
RLdFw x tan (ArgLd)
R
RLdFw
7
X
RLdFw x tan (ArgLd)
R
0
8
X
–0.2143 x RFPP/2
R
0.8 x RFPP/2
9
X
–0.4 x RLdFw x tan(ArgDir=20°)
R
0.4 x RLdFw
10
X
0.5 x X1
R
–0.23 x X1
11
X
0.8 x X1
R
–0.37 x X1
12
X
0.5 x X1
R
0.5 x R1
13
X
0
R
0.5 x RFPP
Table
12
is used in conjunction with figure 31.
set
set
set
set
+ RFPP/2
set
set
+ RFPP/2
set
set
set
set
set
set
set
1MRK502053-UEN B
Comments
ArgLd = angle for the maximal load
transfer
Exact: 0.8 x RFPP/2 (ArgDir=20°)
Exact –0.5 x R1
x
set
tan(ArgNegRes=30°)
Exact –0.5 x R1
x
set
tan(ArgNegRes=30°)
OperationLdCmp
Only used when
setting is 0 (Off)
Generator protection REG670 2.0 IEC
Commissioning manual