Connection Diagram For Collective Detector Line - Siemens FDOOT221 Technical Manual

Automatic fire detectors
Hide thumbs Also See for FDOOT221:
Table of Contents

Advertisement

5
Mounting / installation
Detector lines
5.16.2
92
Building Technologies
Fire Safety

Connection diagram for collective detector line

General
Connect a control panel-specific end-of-line (EOL) to the end of the collective
detector line.
Connecting external alarm indicators
Observe the following points when connecting external alarm indicators:
If the external alarm indicator is connected to only one detector, there is no
limitation.
If the detector FDOOT241-A9 is used in combination with the base adapter
FDB299, there is no limitation.
If the external alarm indicator is connected to more than one detector, this is
only admissible on the following conditions:
All detectors use the Sinteso base FDB20x (do not mix with older base
generations e.g. AlgoRex bases).
No sounder base is used.
The detectors must have the part number and product version (ES) in
question (see table).
Part number
Device version (REV)
FDOOT241-9
A5Q00004813
<13
A5Q00004813
A5Q00015955
13 ES<30
FDOOT241-A9
S54310-F11-A1
This also applies to the flame detector FDF2x1-9 and the linear smoke detector
1
FDL2x1-9
The cabling of the external alarm indicators can be migrated to FDnet without
2
any changes.
External alarm indicator connected to
several collective detectors
not admissible
1
30
permissible
1
permissible
30
permissible
2
2
2
007004_n_en_--
01.07.2012